Vaillant Arotherm+ V2

Chellaston, Derby · Detached · 115 m² · 2012 or newer · 3.5 kW · radiators · installed by Heat Centre

Last 30 days

721 hourly rows · MID-class heat meter present: yes
4.40efficiency (COP) over 721 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
157 kWh
Heat delivered
693 kWh (heat meter)
Estimate without heat meter
flow sensor 3.83 · temperature model 4.14
Mean outdoor temperature
10.2 °C · 208 space-heating hours
Flow temperature at 0 °C outside
28.8 °C (curve slope 0.14 per K)
Flow − return while heating
2.1 K
House needs at −3 °C
0.5 kW (unit rated 3.5 kW) · fit r² 0.15
Hot water
45% of electricity, COP 3.35
warningOnly 2.1 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 45% of electricity at COP 3.35
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 3.5 kW but the house needs about 0.5 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day05102026-10-08: 1.9 kWh, outside 11 °C2026-10-09: 3.8 kWh, outside 13.9 °C2026-10-10: 4.7 kWh, outside 10.3 °C2026-10-11: 4.9 kWh, outside 9.9 °C2026-10-12: 4.8 kWh, outside 13.1 °C2026-10-13: 1.8 kWh, outside 14.8 °C2026-10-14: 3.7 kWh, outside 12.6 °C2026-10-15: 2.4 kWh, outside 15.8 °C2026-10-16: 3.3 kWh, outside 10 °C2026-10-17: 4.9 kWh, outside 7.8 °C2026-10-18: 6.4 kWh, outside 9.3 °C2026-10-19: 4.6 kWh, outside 10.9 °C2026-10-20: 3.7 kWh, outside 10.8 °C2026-10-21: 8.7 kWh, outside 8.3 °C2026-10-22: 5.7 kWh, outside 8.7 °C2026-10-23: 8 kWh, outside 8.9 °C2026-10-24: 2.5 kWh, outside 8.8 °C2026-10-25: 7.6 kWh, outside 10 °C2026-10-26: 0.1 kWh, outside 11 °C2026-10-27: 3.7 kWh, outside 12.9 °C2026-10-28: 9.9 kWh, outside 10.2 °C2026-10-29: 5.4 kWh, outside 10.7 °C2026-10-30: 5.5 kWh, outside 10.4 °C2026-10-31: 5 kWh, outside 8.8 °C2026-11-01: 5.6 kWh, outside 8.3 °C2026-11-02: 7.5 kWh, outside 7.8 °C2026-11-03: 6.8 kWh, outside 8 °C2026-11-04: 7.1 kWh, outside 9 °C2026-11-05: 7.8 kWh, outside 8.3 °C2026-11-06: 7.5 kWh, outside 8.6 °C2026-11-07: 2.2 kWh, outside 6.2 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 3.82026-10-09: COP 4.172026-10-10: COP 4.262026-10-11: COP 3.882026-10-12: COP 4.182026-10-13: COP 3.822026-10-14: COP 3.72026-10-15: COP 3.882026-10-16: COP 3.722026-10-17: COP 4.22026-10-18: COP 4.112026-10-19: COP 4.122026-10-20: COP 4.432026-10-21: COP 4.592026-10-22: COP 4.522026-10-23: COP 4.662026-10-24: COP 4.052026-10-25: COP 4.182026-10-27: COP 4.162026-10-28: COP 4.982026-10-29: COP 4.862026-10-30: COP 4.052026-10-31: COP 4.382026-11-01: COP 4.272026-11-02: COP 4.432026-11-03: COP 5.032026-11-04: COP 4.652026-11-05: COP 4.872026-11-06: COP 4.582026-11-07: COP 4.3810-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.