721 hourly rows · MID-class heat meter present: yes
4.55efficiency (COP) over 721 hours, from the heat meter better than 94% of the metered fleet in January 2026
Electricity used
311 kWh
Heat delivered
1415 kWh (heat meter)
Estimate without heat meter
flow sensor 4.57 · temperature model 4.99
Mean outdoor temperature
12.3 °C · 554 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
41.9 °C (curve slope -0.85 per K)
Flow − return while heating
1.7 K
House needs at −3 °C
4.2 kW (unit rated 6 kW) · fit r² 0.16
Hot water
no hot-water flag in data
warningOnly 1.7 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.