Daikin Altherma 3

Marston Moretaine · Semi-detached · 88 m² · 1900 to 1939 · 9 kW · radiators · installed by Octopus Energy Services

Last 30 days

721 hourly rows · MID-class heat meter present: yes
3.22efficiency (COP) over 721 hours, from the heat meter
better than 24% of the metered fleet in January 2026
Electricity used
226 kWh
Heat delivered
728 kWh (heat meter)
Estimate without heat meter
flow sensor 3.55 · temperature model 4.56
Mean outdoor temperature
10.8 °C · 209 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
35.6 °C (curve slope -0.42 per K)
Flow − return while heating
2.1 K
House needs at −3 °C
2.6 kW (unit rated 9 kW) · fit r² 0.00
Hot water
35% of electricity, COP 2.46
warningOnly 2.1 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 35% of electricity at COP 2.46
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 9 kW but the house needs about 2.6 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £7 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day06132026-10-08: 1.7 kWh, outside 11.5 °C2026-10-09: 4.4 kWh, outside 14.7 °C2026-10-10: 4.3 kWh, outside 10.7 °C2026-10-11: 5.1 kWh, outside 10.7 °C2026-10-12: 6.4 kWh, outside 14.2 °C2026-10-13: 2.2 kWh, outside 15.9 °C2026-10-14: 3.8 kWh, outside 13.1 °C2026-10-15: 2.8 kWh, outside 16.8 °C2026-10-16: 5.4 kWh, outside 11.4 °C2026-10-17: 10.1 kWh, outside 8.5 °C2026-10-18: 7.6 kWh, outside 9.4 °C2026-10-19: 6.8 kWh, outside 10.9 °C2026-10-20: 7.6 kWh, outside 11.1 °C2026-10-21: 10.3 kWh, outside 8.2 °C2026-10-22: 8.9 kWh, outside 10.3 °C2026-10-23: 9.4 kWh, outside 9.9 °C2026-10-24: 12.7 kWh, outside 9.7 °C2026-10-25: 10.8 kWh, outside 10.2 °C2026-10-26: 5.9 kWh, outside 11.6 °C2026-10-27: 4.1 kWh, outside 13 °C2026-10-28: 7 kWh, outside 10.7 °C2026-10-29: 6 kWh, outside 11.6 °C2026-10-30: 6.7 kWh, outside 11.3 °C2026-10-31: 8.9 kWh, outside 9.4 °C2026-11-01: 9.4 kWh, outside 8.5 °C2026-11-02: 10.2 kWh, outside 8.8 °C2026-11-03: 11.7 kWh, outside 8.7 °C2026-11-04: 10.9 kWh, outside 8.9 °C2026-11-05: 9.1 kWh, outside 8.5 °C2026-11-06: 9.3 kWh, outside 8.7 °C2026-11-07: 7 kWh, outside 4.2 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 3.512026-10-09: COP 3.692026-10-10: COP 2.592026-10-11: COP 2.832026-10-12: COP 3.182026-10-13: COP 1.82026-10-14: COP 2.832026-10-15: COP 2.672026-10-16: COP 2.982026-10-17: COP 3.072026-10-18: COP 2.692026-10-19: COP 3.372026-10-20: COP 3.572026-10-21: COP 3.322026-10-22: COP 3.422026-10-23: COP 3.642026-10-24: COP 3.582026-10-25: COP 3.372026-10-26: COP 3.122026-10-27: COP 3.042026-10-28: COP 3.122026-10-29: COP 2.852026-10-30: COP 3.372026-10-31: COP 3.422026-11-01: COP 3.172026-11-02: COP 3.212026-11-03: COP 3.262026-11-04: COP 3.342026-11-05: COP 3.252026-11-06: COP 3.322026-11-07: COP 2.5810-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.