Heatproof
Home / system #1150

Grant Aerona HP290

Jersey, Channel Islands · End-terrace · 135 m² · Pre-1900 · 6.5 kW · radiators · installed by Ryan Sharp

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: yes
4.07efficiency (COP) over 721 hours, from the heat meter
better than 81% of the metered fleet in January 2026
Electricity used
557 kWh
Heat delivered
2268 kWh (heat meter)
Estimate without heat meter
flow sensor 4.13 · temperature model 4.07
Mean outdoor temperature
8.3 °C · 646 space-heating hours
Flow temperature at 0 °C outside
40.0 °C (curve slope -0.75 per K)
Flow − return while heating
2.6 K
House needs at −3 °C
4.5 kW (unit rated 6.5 kW) · fit r² 0.18
Hot water
20% of electricity, COP 3.77
warningOnly 2.6 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day016322026-01-05: 31.6 kWh, outside 3.3 °C2026-01-06: 31.4 kWh, outside 4.7 °C2026-01-07: 21.7 kWh, outside 8.5 °C2026-01-08: 20.5 kWh, outside 9.4 °C2026-01-09: 21.5 kWh, outside 7.8 °C2026-01-10: 22.1 kWh, outside 6.6 °C2026-01-11: 19.9 kWh, outside 8.2 °C2026-01-12: 15.7 kWh, outside 10.6 °C2026-01-13: 15.7 kWh, outside 10.3 °C2026-01-14: 15.1 kWh, outside 9.9 °C2026-01-15: 16.6 kWh, outside 9.2 °C2026-01-16: 17.6 kWh, outside 8.8 °C2026-01-17: 19 kWh, outside 7.8 °C2026-01-18: 18.5 kWh, outside 9.3 °C2026-01-19: 15.7 kWh, outside 9.3 °C2026-01-20: 17.1 kWh, outside 8.5 °C2026-01-21: 15.9 kWh, outside 9.5 °C2026-01-22: 16 kWh, outside 9 °C2026-01-23: 17.8 kWh, outside 7.9 °C2026-01-24: 18.9 kWh, outside 8.1 °C2026-01-25: 18.7 kWh, outside 7.7 °C2026-01-26: 19.4 kWh, outside 7.6 °C2026-01-27: 14.2 kWh, outside 9.4 °C2026-01-28: 16.6 kWh, outside 7.6 °C2026-01-29: 18.3 kWh, outside 6.8 °C2026-01-30: 15.5 kWh, outside 9 °C2026-01-31: 15.5 kWh, outside 8.4 °C2026-02-01: 16.4 kWh, outside 8.9 °C2026-02-02: 19.4 kWh, outside 7.4 °C2026-02-03: 13.8 kWh, outside 9.4 °C2026-02-04: 0.6 kWh, outside 8.1 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 3.412026-01-06: COP 3.482026-01-07: COP 4.212026-01-08: COP 4.372026-01-09: COP 42026-01-10: COP 3.732026-01-11: COP 3.952026-01-12: COP 4.42026-01-13: COP 4.522026-01-14: COP 4.362026-01-15: COP 4.362026-01-16: COP 4.282026-01-17: COP 42026-01-18: COP 3.932026-01-19: COP 4.132026-01-20: COP 4.282026-01-21: COP 4.462026-01-22: COP 4.272026-01-23: COP 4.232026-01-24: COP 4.362026-01-25: COP 4.132026-01-26: COP 3.962026-01-27: COP 4.182026-01-28: COP 42026-01-29: COP 4.132026-01-30: COP 4.192026-01-31: COP 4.012026-02-01: COP 3.962026-02-02: COP 4.052026-02-03: COP 4.132026-02-04: COP 3.6401-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060024681012outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.