Home / system #1205

Grant Aerona HP290

Carshalton, Sutton · Semi-detached · 129 m² · 1940 to 1982 · 9 kW · radiators · installed by Asset Plumbing & Heating Ltd

Last 7 days

169 hourly rows · MID-class heat meter present: yes
3.86efficiency (COP) over 169 hours, from the heat meter
better than 65% of the metered fleet in January 2026
Electricity used
128 kWh
Heat delivered
493 kWh (heat meter)
Estimate without heat meter
flow sensor 3.86 · temperature model 4.15
Mean outdoor temperature
10.1 °C · 138 space-heating hours
Flow temperature at 0 °C outside
42.1 °C (curve slope -0.70 per K)
Flow − return while heating
1.6 K
House needs at −3 °C
4.7 kW (unit rated 9 kW) · fit r² 0.36
Hot water
29% of electricity, COP 3.22
warningOnly 1.6 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day011212026-10-31: 7.9 kWh, outside 12.2 °C2026-11-01: 16.6 kWh, outside 10.2 °C2026-11-02: 16.2 kWh, outside 10.3 °C2026-11-03: 16.7 kWh, outside 10.2 °C2026-11-04: 19.9 kWh, outside 10 °C2026-11-05: 19.4 kWh, outside 9.9 °C2026-11-06: 21.4 kWh, outside 10 °C2026-11-07: 9.5 kWh, outside 5.4 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.12026-11-01: COP 3.912026-11-02: COP 3.972026-11-03: COP 4.032026-11-04: COP 3.842026-11-05: COP 3.882026-11-06: COP 3.672026-11-07: COP 3.4710-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050603579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.