Heatproof
Home / system #1223

Vaillant Arotherm+

Horsham, West Sussex · Detached · 184 m² · 2012 or newer · 5 kW · underfloor · installed by Revolution Heating

Last 7 days

168 hourly rows · MID-class heat meter present: yes
4.92efficiency (COP) over 168 hours, from the heat meter
better than 98% of the metered fleet in January 2026
Electricity used
68 kWh
Heat delivered
336 kWh (heat meter)
Estimate without heat meter
flow sensor 4.73 · temperature model 4.80
Mean outdoor temperature
8.4 °C · 137 space-heating hours
Flow temperature at 0 °C outside
31.6 °C (curve slope -0.43 per K)
Flow − return while heating
2.0 K
House needs at −3 °C
3.4 kW (unit rated 5 kW) · fit r² 0.30
Hot water
24% of electricity, COP 3.67
warningOnly 2 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day05102026-10-31: 5.4 kWh, outside 10.9 °C2026-11-01: 9.2 kWh, outside 7.9 °C2026-11-02: 8.7 kWh, outside 9.1 °C2026-11-03: 9.5 kWh, outside 9.4 °C2026-11-04: 9.3 kWh, outside 8.3 °C2026-11-05: 10.4 kWh, outside 8.2 °C2026-11-06: 10.3 kWh, outside 7.6 °C2026-11-07: 5.5 kWh, outside 3.6 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.732026-11-01: COP 4.982026-11-02: COP 5.112026-11-03: COP 4.912026-11-04: COP 5.032026-11-05: COP 4.92026-11-06: COP 5.022026-11-07: COP 4.3510-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060135791113outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.