Heatproof
Home / system #122

Mitsubishi Ecodan

Lightwater · End-terrace · 100 m² · 1940 to 1982 · 6 kW · underfloor · installed by Rob Whitney

1–31 Dec 2025

745 hourly rows · MID-class heat meter present: yes
3.25efficiency (COP) over 745 hours, from the heat meter
better than 24% of the metered fleet in January 2026
Electricity used
499 kWh
Heat delivered
1623 kWh (heat meter)
Estimate without heat meter
flow sensor 3.26 · temperature model 3.69
Mean outdoor temperature
7.3 °C · 605 space-heating hours
Flow temperature at 0 °C outside
36.8 °C (curve slope -0.14 per K)
Flow − return while heating
2.7 K
House needs at −3 °C
3.1 kW (unit rated 6 kW) · fit r² 0.02
Hot water
no hot-water flag in data
warningOnly 2.7 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
valueReaching the fleet’s January median (3.69) would have saved about £15 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day015302025-12-01: 15.8 kWh, outside 9.9 °C2025-12-02: 13.1 kWh, outside 8 °C2025-12-03: 16.6 kWh, outside 6.1 °C2025-12-04: 18 kWh, outside 6.3 °C2025-12-05: 26.1 kWh, outside 5.6 °C2025-12-06: 14.6 kWh, outside 9.9 °C2025-12-07: 11.6 kWh, outside 11.1 °C2025-12-08: 10.5 kWh, outside 12 °C2025-12-09: 10.6 kWh, outside 12.1 °C2025-12-10: 9.6 kWh, outside 10.2 °C2025-12-11: 15.7 kWh, outside 9.3 °C2025-12-12: 11.8 kWh, outside 9 °C2025-12-13: 18.3 kWh, outside 6.8 °C2025-12-14: 17 kWh, outside 9 °C2025-12-15: 12.9 kWh, outside 10 °C2025-12-16: 10 kWh, outside 8.5 °C2025-12-17: 17.5 kWh, outside 6 °C2025-12-18: 10.7 kWh, outside 10.7 °C2025-12-19: 15.6 kWh, outside 7.7 °C2025-12-20: 18.1 kWh, outside 6.2 °C2025-12-21: 13.4 kWh, outside 8.8 °C2025-12-22: 11 kWh, outside 9.3 °C2025-12-23: 14.9 kWh, outside 6.6 °C2025-12-24: 18.8 kWh, outside 4.5 °C2025-12-25: 19.7 kWh, outside 3.1 °C2025-12-26: 21.6 kWh, outside 3.5 °C2025-12-27: 18.9 kWh, outside 4.8 °C2025-12-28: 17.2 kWh, outside 5.9 °C2025-12-29: 17.9 kWh, outside 4.6 °C2025-12-30: 21.5 kWh, outside 3.1 °C2025-12-31: 29.6 kWh, outside -1.1 °C2026-01-01: 0.5 kWh, outside -1.2 °Cdaily COP (heat ÷ electricity)1352025-12-01: COP 3.672025-12-02: COP 3.562025-12-03: COP 3.222025-12-04: COP 3.272025-12-05: COP 2.72025-12-06: COP 3.612025-12-07: COP 3.522025-12-08: COP 3.752025-12-09: COP 3.662025-12-10: COP 3.692025-12-11: COP 3.462025-12-12: COP 3.642025-12-13: COP 3.122025-12-14: COP 3.442025-12-15: COP 3.62025-12-16: COP 3.552025-12-17: COP 3.222025-12-18: COP 3.62025-12-19: COP 3.252025-12-20: COP 3.132025-12-21: COP 3.562025-12-22: COP 3.582025-12-23: COP 3.372025-12-24: COP 2.992025-12-25: COP 3.032025-12-26: COP 3.112025-12-27: COP 3.322025-12-28: COP 3.292025-12-29: COP 3.142025-12-30: COP 2.872025-12-31: COP 2.4912-0112-0512-0912-1312-1712-2112-2512-29
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-5-21471013outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.