Home / system #1263
Mitsubishi Ecodan
Shetland · Bungalow · 145 m² · 2012 or newer · 8.5 kW · underfloor · installed by L & S Hunter Ltd
Last 7 days
168 hourly rows · MID-class heat meter present: no
3.47efficiency (COP) over 168 hours, from the heat meter
better than 36% of the metered fleet in January 2026
better than 36% of the metered fleet in January 2026
- Electricity used
- 61 kWh
- Heat delivered
- 210 kWh (heat meter)
- Estimate without heat meter
- flow sensor 3.52 · temperature model 4.85
- Mean outdoor temperature
- 9.2 °C · 79 space-heating hours
- Flow temperature at 0 °C outside
- 33.6 °C (curve slope -0.58 per K)
- Flow − return while heating
- 2.9 K
- House needs at −3 °C
- 2.7 kW (unit rated 8.5 kW) · fit r² 0.04
- Hot water
- 40% of electricity, COP 3.07
warningOnly 2.9 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 40% of electricity at COP 3.07
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
warningUnit is rated 8.5 kW but the house needs about 2.7 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £1 in this window at 0.25 GBP/kWh. An estimate, not a promise.