Heatproof
Home / system #1264

Grant Aerona HP290

Shirebrook, Mansfield · End-terrace · 141 m² · 2012 or newer · 4 kW · radiators · installed by Ipsum Renewables

Last 7 days

169 hourly rows · MID-class heat meter present: yes
3.68efficiency (COP) over 169 hours, from the heat meter
better than 50% of the metered fleet in January 2026
Electricity used
25 kWh
Heat delivered
91 kWh (heat meter)
Estimate without heat meter
flow sensor 3.60 · temperature model 3.26
Mean outdoor temperature
8.8 °C · 7 space-heating hours
Flow temperature at 0 °C outside
32.6 °C (curve slope -0.30 per K)
Flow − return while heating
2.2 K
House needs at −3 °C
1.1 kW (unit rated 4 kW) · fit r² 0.00
Hot water
85% of electricity, COP 3.64
infoOnly 7 space-heating hours in this window
Space-heating findings need at least 60 hours with the compressor running below 15 °C outside. Choose a winter window or come back during the heating season.
valueReaching the fleet’s January median (3.69) would have saved about £0 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day0242026-10-31: 1.3 kWh, outside 9.8 °C2026-11-01: 4.3 kWh, outside 7.8 °C2026-11-02: 2.4 kWh, outside 8.1 °C2026-11-03: 2.7 kWh, outside 8.7 °C2026-11-04: 2.8 kWh, outside 9.6 °C2026-11-05: 4.3 kWh, outside 9.1 °C2026-11-06: 4.4 kWh, outside 9.3 °C2026-11-07: 2.6 kWh, outside 7.4 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.932026-11-01: COP 3.392026-11-02: COP 3.332026-11-03: COP 3.582026-11-04: COP 3.672026-11-05: COP 3.822026-11-06: COP 3.962026-11-07: COP 3.710-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.