Heatproof
Home / system #1282

Grant Aerona HP290

Leatherhead, Surrey · Semi-detached · 96 m² · 1940 to 1982 · 6.5 kW · radiators

Last 30 days

721 hourly rows · MID-class heat meter present: yes
3.15efficiency (COP) over 721 hours, from the heat meter
better than 23% of the metered fleet in January 2026
Electricity used
267 kWh
Heat delivered
842 kWh (heat meter)
Estimate without heat meter
flow sensor 2.09 · temperature model 4.87
Mean outdoor temperature
10.6 °C · 312 space-heating hours · cooling 1 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
36.5 °C (curve slope -0.68 per K)
Flow − return while heating
2.5 K
House needs at −3 °C
3.7 kW (unit rated 6.5 kW) · fit r² 0.37
Hot water
35% of electricity, COP 2.64
warningOnly 2.5 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 35% of electricity at COP 2.64
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
valueReaching the fleet’s January median (3.69) would have saved about £10 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day08172026-10-08: 3.6 kWh, outside – °C2026-10-09: 7.5 kWh, outside – °C2026-10-10: 10.2 kWh, outside – °C2026-10-11: 5.8 kWh, outside – °C2026-10-12: 3.4 kWh, outside – °C2026-10-13: 3.2 kWh, outside – °C2026-10-14: 2.1 kWh, outside – °C2026-10-15: 2 kWh, outside – °C2026-10-16: 2.2 kWh, outside – °C2026-10-17: 2.8 kWh, outside – °C2026-10-18: 9 kWh, outside – °C2026-10-19: 9.8 kWh, outside – °C2026-10-20: 7 kWh, outside – °C2026-10-21: 12.2 kWh, outside – °C2026-10-22: 9.6 kWh, outside 12 °C2026-10-23: 12.4 kWh, outside 9.8 °C2026-10-24: 16.6 kWh, outside 10.2 °C2026-10-25: 14.2 kWh, outside 10.5 °C2026-10-26: 8.4 kWh, outside 12.6 °C2026-10-27: 5.1 kWh, outside 13.6 °C2026-10-28: 7.6 kWh, outside 12.1 °C2026-10-29: 7 kWh, outside 13.2 °C2026-10-30: 7.1 kWh, outside 10.9 °C2026-10-31: 11 kWh, outside 10.7 °C2026-11-01: 12.8 kWh, outside 9.7 °C2026-11-02: 12.2 kWh, outside 9.2 °C2026-11-03: 11.8 kWh, outside 9.6 °C2026-11-04: 12.6 kWh, outside 9.4 °C2026-11-05: 15.8 kWh, outside 9.5 °C2026-11-06: 14.6 kWh, outside 8.8 °C2026-11-07: 7.8 kWh, outside 5.7 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 4.342026-10-09: COP 3.992026-10-10: COP 2.342026-10-11: COP 2.632026-10-12: COP 3.552026-10-13: COP 2.922026-10-14: COP 2.732026-10-15: COP 2.92026-10-16: COP 1.762026-10-17: COP 4.062026-10-18: COP 3.062026-10-19: COP 3.222026-10-20: COP 3.652026-10-21: COP 3.372026-10-22: COP 3.422026-10-23: COP 3.092026-10-24: COP 2.672026-10-25: COP 2.692026-10-26: COP 3.322026-10-27: COP 3.212026-10-28: COP 3.142026-10-29: COP 3.382026-10-30: COP 3.662026-10-31: COP 3.422026-11-01: COP 3.232026-11-02: COP 3.382026-11-03: COP 3.332026-11-04: COP 3.342026-11-05: COP 2.732026-11-06: COP 3.052026-11-07: COP 2.710-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506046810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.