Home / system #1283

Vaillant Arotherm+

Crawley · Detached · 272 m² · 1983 to 2011 · 12 kW · underfloor · installed by Urban Plumbers Ltd

Last 30 days

721 hourly rows · MID-class heat meter present: yes
4.94efficiency (COP) over 721 hours, from the heat meter
better than 98% of the metered fleet in January 2026
Electricity used
500 kWh
Heat delivered
2469 kWh (heat meter)
Estimate without heat meter
flow sensor 4.38 · temperature model 4.78
Mean outdoor temperature
11.0 °C · 497 space-heating hours
Flow temperature at 0 °C outside
36.3 °C (curve slope -0.52 per K)
Flow − return while heating
1.6 K
House needs at −3 °C
6.2 kW (unit rated 12 kW) · fit r² 0.13
Hot water
24% of electricity, COP 4.14
warningOnly 1.6 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day013272026-10-08: 8.9 kWh, outside 11.7 °C2026-10-09: 12.5 kWh, outside 15 °C2026-10-10: 17.1 kWh, outside 11 °C2026-10-11: 14.4 kWh, outside 11.5 °C2026-10-12: 5.6 kWh, outside 14.5 °C2026-10-13: 4.9 kWh, outside 16.2 °C2026-10-14: 9.3 kWh, outside 12.6 °C2026-10-15: 5 kWh, outside 16.7 °C2026-10-16: 9.9 kWh, outside 12.4 °C2026-10-17: 17.9 kWh, outside 8.9 °C2026-10-18: 18.1 kWh, outside 9.2 °C2026-10-19: 14.9 kWh, outside 10.2 °C2026-10-20: 13.6 kWh, outside 10.7 °C2026-10-21: 16.3 kWh, outside 9.1 °C2026-10-22: 15.4 kWh, outside 11.7 °C2026-10-23: 16.9 kWh, outside 10.1 °C2026-10-24: 19.5 kWh, outside 10.5 °C2026-10-25: 22.6 kWh, outside 10.7 °C2026-10-26: 14 kWh, outside 12.2 °C2026-10-27: 15.4 kWh, outside 13.3 °C2026-10-28: 19.1 kWh, outside 10.9 °C2026-10-29: 14.6 kWh, outside 11.7 °C2026-10-30: 20.3 kWh, outside 10.5 °C2026-10-31: 18.7 kWh, outside 10.1 °C2026-11-01: 23.6 kWh, outside 7.9 °C2026-11-02: 21.1 kWh, outside 9.1 °C2026-11-03: 22 kWh, outside 9.4 °C2026-11-04: 26.9 kWh, outside 8.2 °C2026-11-05: 24.2 kWh, outside 8.2 °C2026-11-06: 25.8 kWh, outside 7.6 °C2026-11-07: 11.5 kWh, outside 3.5 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 5.072026-10-09: COP 5.262026-10-10: COP 5.152026-10-11: COP 4.782026-10-12: COP 5.562026-10-13: COP 5.022026-10-14: COP 5.342026-10-15: COP 4.82026-10-16: COP 5.522026-10-17: COP 4.752026-10-18: COP 4.782026-10-19: COP 5.22026-10-20: COP 5.412026-10-21: COP 5.22026-10-22: COP 4.932026-10-23: COP 5.192026-10-24: COP 4.942026-10-25: COP 4.742026-10-26: COP 5.32026-10-27: COP 5.142026-10-28: COP 4.872026-10-29: COP 5.312026-10-30: COP 4.842026-10-31: COP 52026-11-01: COP 4.682026-11-02: COP 4.942026-11-03: COP 4.92026-11-04: COP 4.572026-11-05: COP 4.812026-11-06: COP 4.612026-11-07: COP 4.1110-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506013579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.