Heatproof
Home / system #1296

Vaillant Arotherm+

Swansea, West Glamorgan · Detached · 220 m² · 1940 to 1982 · 12 kW · radiators · installed by Greenlands Energy

Last 30 days

720 hourly rows · MID-class heat meter present: yes
3.68efficiency (COP) over 720 hours, from the heat meter
better than 50% of the metered fleet in January 2026
Electricity used
511 kWh
Heat delivered
1883 kWh (heat meter)
Estimate without heat meter
flow sensor 3.65 · temperature model 4.00
Mean outdoor temperature
11.5 °C · 277 space-heating hours
Flow temperature at 0 °C outside
35.1 °C (curve slope 0.07 per K)
Flow − return while heating
3.2 K
House needs at −3 °C
6.4 kW (unit rated 12 kW) · fit r² 0.00
Hot water
4% of electricity, COP 2.95
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
valueReaching the fleet’s January median (3.69) would have saved about £0 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day017352026-10-08: 10.4 kWh, outside 13.7 °C2026-10-09: 10.2 kWh, outside 15 °C2026-10-10: 18.6 kWh, outside 12.4 °C2026-10-11: 16.9 kWh, outside 12.2 °C2026-10-12: 3 kWh, outside 16.2 °C2026-10-13: 8.4 kWh, outside 15.8 °C2026-10-14: 5.7 kWh, outside 15.1 °C2026-10-15: 0.1 kWh, outside 15.9 °C2026-10-16: 24 kWh, outside 11 °C2026-10-17: 34.7 kWh, outside 8.8 °C2026-10-18: 32.5 kWh, outside 8.6 °C2026-10-19: 21.4 kWh, outside 10.1 °C2026-10-20: 20.9 kWh, outside 9.8 °C2026-10-21: 20.2 kWh, outside 10.9 °C2026-10-22: 18.6 kWh, outside 11.8 °C2026-10-23: 19.5 kWh, outside 10.2 °C2026-10-24: 16.8 kWh, outside 12.1 °C2026-10-25: 20.4 kWh, outside 11.6 °C2026-10-26: 10.4 kWh, outside 13.9 °C2026-10-27: 12.2 kWh, outside 13 °C2026-10-28: 9.2 kWh, outside 13.2 °C2026-10-29: 8.4 kWh, outside 12.2 °C2026-10-30: 10.8 kWh, outside 11.3 °C2026-10-31: 10.9 kWh, outside 9.8 °C2026-11-01: 18.6 kWh, outside 8.7 °C2026-11-02: 24.3 kWh, outside 9.2 °C2026-11-03: 26.4 kWh, outside 8.8 °C2026-11-04: 24.9 kWh, outside 9.5 °C2026-11-05: 23.6 kWh, outside 8.7 °C2026-11-06: 21.8 kWh, outside 8.8 °C2026-11-07: 7.5 kWh, outside 8.1 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 4.312026-10-09: COP 4.052026-10-10: COP 3.812026-10-11: COP 3.962026-10-12: COP 5.592026-10-13: COP 3.092026-10-14: COP 4.092026-10-16: COP 3.32026-10-17: COP 2.812026-10-18: COP 2.762026-10-19: COP 3.492026-10-20: COP 3.52026-10-21: COP 3.632026-10-22: COP 3.732026-10-23: COP 3.562026-10-24: COP 3.972026-10-25: COP 3.782026-10-26: COP 4.782026-10-27: COP 4.432026-10-28: COP 4.642026-10-29: COP 4.912026-10-30: COP 4.272026-10-31: COP 4.582026-11-01: COP 3.632026-11-02: COP 3.82026-11-03: COP 3.52026-11-04: COP 3.642026-11-05: COP 3.772026-11-06: COP 3.732026-11-07: COP 3.4410-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506013579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.