Vaillant Arotherm+
Birmingham · Detached · 115 m² · 1940 to 1982 · 5 kW · underfloor · installed by Smart Boiler Company
Last 7 days
169 hourly rows · MID-class heat meter present: yes
4.81efficiency (COP) over 169 hours, from the heat meter
better than 98% of the metered fleet in January 2026
better than 98% of the metered fleet in January 2026
- Electricity used
- 73 kWh
- Heat delivered
- 352 kWh (heat meter)
- Estimate without heat meter
- flow sensor 4.87 · temperature model 4.51
- Mean outdoor temperature
- 8.2 °C · 144 space-heating hours
- Flow temperature at 0 °C outside
- 26.2 °C (curve slope 0.58 per K)
- Flow − return while heating
- 2.7 K
- House needs at −3 °C
- 2.3 kW (unit rated 5 kW) · fit r² 0.00
- Hot water
- no hot-water flag in data
warningOnly 2.7 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
infoUnit is rated 5 kW but the house needs about 2.3 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C