Heatproof
Home / system #1312

Vaillant Arotherm+

Pool in Wharfedale, West Yorkshire · Detached · 200 m² · 2012 or newer · 7 kW · radiators · installed by Clear Skies Energy Ltd

Last 7 days

169 hourly rows · MID-class heat meter present: yes
3.87efficiency (COP) over 169 hours, from the heat meter
better than 65% of the metered fleet in January 2026
Electricity used
75 kWh
Heat delivered
290 kWh (heat meter)
Estimate without heat meter
flow sensor 3.49 · temperature model 3.92
Mean outdoor temperature
8.7 °C · 52 space-heating hours · cooling 1 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
43.3 °C (curve slope -1.13 per K)
Flow − return while heating
2.4 K
House needs at −3 °C
11.3 kW (unit rated 7 kW) · fit r² 0.31
Hot water
30% of electricity, COP 3.23
infoOnly 52 space-heating hours in this window
Space-heating findings need at least 60 hours with the compressor running below 15 °C outside. Choose a winter window or come back during the heating season.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day07152026-10-31: 5.9 kWh, outside 8.1 °C2026-11-01: 14 kWh, outside 7.7 °C2026-11-02: 14.6 kWh, outside 8 °C2026-11-03: 9.3 kWh, outside 9 °C2026-11-04: 8.6 kWh, outside 9.3 °C2026-11-05: 8.4 kWh, outside 9.4 °C2026-11-06: 9.8 kWh, outside 9.2 °C2026-11-07: 4.4 kWh, outside 7.6 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.642026-11-01: COP 3.82026-11-02: COP 3.762026-11-03: COP 3.942026-11-04: COP 4.032026-11-05: COP 3.872026-11-06: COP 3.962026-11-07: COP 3.910-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.