Home / system #1366
Vaillant Arotherm+
Derby, Derbyshire · Detached · 193 m² · 1940 to 1982 · 10 kW · underfloor
5 Jan – 4 Feb 2026 (winter reference)
81 hourly rows · MID-class heat meter present: yes
4.02efficiency (COP) over 81 hours, from the heat meter
better than 77% of the metered fleet in January 2026
better than 77% of the metered fleet in January 2026
- Electricity used
- 111 kWh
- Heat delivered
- 447 kWh (heat meter)
- Estimate without heat meter
- flow sensor 4.05 · temperature model 3.48
- Mean outdoor temperature
- 4.9 °C · 72 space-heating hours
- Flow temperature at 0 °C outside
- 37.0 °C (curve slope -0.52 per K)
- Flow − return while heating
- 2.9 K
- House needs at −3 °C
- 8.4 kW (unit rated 10 kW) · fit r² 0.23
- Hot water
- 15% of electricity, COP 3.32
warningOnly 2.9 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.