Heatproof
Home / system #1375

Daikin Altherma 3

Pudsey, West Yorkshire · Bungalow · 90 m² · 1940 to 1982 · 8 kW · radiators · installed by Octopus Energy Services

Last 7 days

169 hourly rows · MID-class heat meter present: no
5.46efficiency (COP) over 169 hours, from the heat meter
better than 99% of the metered fleet in January 2026
Electricity used
78 kWh
Heat delivered
429 kWh (heat meter)
Estimate without heat meter
flow sensor 5.57 · temperature model 4.15
Mean outdoor temperature
8.3 °C · 133 space-heating hours
Flow temperature at 0 °C outside
38.7 °C (curve slope -0.65 per K)
Flow − return while heating
5.1 K
House needs at −3 °C
2.8 kW (unit rated 8 kW) · fit r² 0.00
Hot water
21% of electricity, COP 4.39
infoUnit is rated 8 kW but the house needs about 2.8 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day06122026-10-31: 6.3 kWh, outside 8.3 °C2026-11-01: 12.1 kWh, outside 7.9 °C2026-11-02: 12.4 kWh, outside 7.6 °C2026-11-03: 10.1 kWh, outside 8.5 °C2026-11-04: 11.3 kWh, outside 8.7 °C2026-11-05: 9.4 kWh, outside 8.7 °C2026-11-06: 11.6 kWh, outside 8.7 °C2026-11-07: 5.2 kWh, outside 7.8 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 5.332026-11-01: COP 5.482026-11-02: COP 5.362026-11-03: COP 5.592026-11-04: COP 5.492026-11-05: COP 5.292026-11-06: COP 5.742026-11-07: COP 5.2310-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060456789101112outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.