Grant Aerona HP290
Neath, Neath Port Talbot · Detached · 99 m² · 1940 to 1982 · 6.5 kW · underfloor · installed by WDS Green Energy Ltd
Last 7 days
169 hourly rows · MID-class heat meter present: yes
3.76efficiency (COP) over 169 hours, from the heat meter
better than 59% of the metered fleet in January 2026
better than 59% of the metered fleet in January 2026
- Electricity used
- 44 kWh
- Heat delivered
- 166 kWh (heat meter)
- Estimate without heat meter
- flow sensor – · temperature model 4.36
- Mean outdoor temperature
- 9.2 °C · 62 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 34.2 °C (curve slope -0.11 per K)
- Flow − return while heating
- 2.3 K
- House needs at −3 °C
- 4.3 kW (unit rated 6.5 kW) · fit r² 0.11
- Hot water
- no hot-water flag in data
warningOnly 2.3 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.