Heatproof
Home / system #1378

Vaillant Arotherm+ V2

Westbury-on-Trym, Bristol · Detached · 161 m² · 1940 to 1982 · 7 kW · underfloor · installed by Rickman Renewables

Last 7 days

169 hourly rows · MID-class heat meter present: yes
5.11efficiency (COP) over 169 hours, from the heat meter
better than 99% of the metered fleet in January 2026
Electricity used
105 kWh
Heat delivered
536 kWh (heat meter)
Estimate without heat meter
flow sensor 5.15 · temperature model 4.11
Mean outdoor temperature
9.1 °C · 157 space-heating hours
Flow temperature at 0 °C outside
39.0 °C (curve slope -0.52 per K)
Flow − return while heating
2.2 K
House needs at −3 °C
4.9 kW (unit rated 7 kW) · fit r² 0.19
Hot water
14% of electricity, COP 4.09
warningOnly 2.2 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day08162026-10-31: 11.2 kWh, outside 10.4 °C2026-11-01: 14.6 kWh, outside 8.9 °C2026-11-02: 16.1 kWh, outside 9.4 °C2026-11-03: 16.3 kWh, outside 8.8 °C2026-11-04: 13.2 kWh, outside 9.6 °C2026-11-05: 15.2 kWh, outside 8.7 °C2026-11-06: 13.4 kWh, outside 9 °C2026-11-07: 4.8 kWh, outside 7.9 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.62026-11-01: COP 5.222026-11-02: COP 5.032026-11-03: COP 4.962026-11-04: COP 5.322026-11-05: COP 5.12026-11-06: COP 5.412026-11-07: COP 5.410-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506034567891011121314outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.