Home / system #204

Stiebel Eltron WPE-I 12 H

Caersws, Mid Wales · Detached · 251 m² · 2012 or newer · 12 kW · underfloor · installed by Richard Burrows

Last 7 days

169 hourly rows · MID-class heat meter present: yes
6.89efficiency (COP) over 169 hours, from the heat meter
better than 100% of the metered fleet in January 2026
Electricity used
43 kWh
Heat delivered
294 kWh (heat meter)
Estimate without heat meter
flow sensor 7.14 · temperature model 4.87
Mean outdoor temperature
8.6 °C · 64 space-heating hours
Flow temperature at 0 °C outside
27.5 °C (curve slope 0.12 per K)
Flow − return while heating
5.9 K
House needs at −3 °C
4.3 kW (unit rated 12 kW) · fit r² 0.01
Hot water
25% of electricity, COP 4.65
infoUnit is rated 12 kW but the house needs about 4.3 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day0482026-10-31: 1.7 kWh, outside 9.9 °C2026-11-01: 6 kWh, outside 7.8 °C2026-11-02: 5.4 kWh, outside 7.6 °C2026-11-03: 6.4 kWh, outside 8.9 °C2026-11-04: 7 kWh, outside 10 °C2026-11-05: 7.6 kWh, outside 8.8 °C2026-11-06: 7.1 kWh, outside 8.4 °C2026-11-07: 1.3 kWh, outside 6.4 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.112026-11-01: COP 6.782026-11-02: COP 6.862026-11-03: COP 7.162026-11-04: COP 7.142026-11-05: COP 7.092026-11-06: COP 7.122026-11-07: COP 7.3810-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050603456789101112outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.