721 hourly rows · MID-class heat meter present: yes
4.13efficiency (COP) over 721 hours, from the heat meter better than 84% of the metered fleet in January 2026
Electricity used
534 kWh
Heat delivered
2206 kWh (heat meter)
Estimate without heat meter
flow sensor 3.98 · temperature model 4.39
Mean outdoor temperature
10.6 °C · 246 space-heating hours · cooling 1 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
34.6 °C (curve slope -0.14 per K)
Flow − return while heating
3.2 K
House needs at −3 °C
5.4 kW (unit rated 12 kW) · fit r² 0.00
Hot water
28% of electricity, COP 3.86
infoUnit is rated 12 kW but the house needs about 5.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.