Clivet Edge F
Dunholme, Lincoln, Lincolnshire · Detached · 175 m² · 1983 to 2011 · 12 kW · underfloor · installed by GlowGroup
Last 7 days
169 hourly rows · MID-class heat meter present: yes
4.01efficiency (COP) over 169 hours, from the heat meter
better than 76% of the metered fleet in January 2026
better than 76% of the metered fleet in January 2026
- Electricity used
- 182 kWh
- Heat delivered
- 731 kWh (heat meter)
- Estimate without heat meter
- flow sensor 3.94 · temperature model 3.94
- Mean outdoor temperature
- 8.8 °C · 85 space-heating hours · cooling 0 kWh removed (1 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 33.0 °C (curve slope 0.16 per K)
- Flow − return while heating
- 3.2 K
- House needs at −3 °C
- 3.2 kW (unit rated 12 kW) · fit r² 0.02
- Hot water
- 28% of electricity, COP 3.83
infoUnit is rated 12 kW but the house needs about 3.2 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C