721 hourly rows · MID-class heat meter present: yes
3.89efficiency (COP) over 721 hours, from the heat meter better than 66% of the metered fleet in January 2026
Electricity used
455 kWh
Heat delivered
1771 kWh (heat meter)
Estimate without heat meter
flow sensor 3.90 · temperature model 3.91
Mean outdoor temperature
5.8 °C · 564 space-heating hours
Flow temperature at 0 °C outside
32.1 °C (curve slope 0.11 per K)
Flow − return while heating
3.0 K
House needs at −3 °C
2.4 kW (unit rated 5 kW) · fit r² 0.00
Hot water
24% of electricity, COP 3.73
infoUnit is rated 5 kW but the house needs about 2.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.