Viessmann Vitocal 151A

Great Haseley, Oxfordshire · Detached · 212 m² · 2012 or newer · 10 kW · underfloor · installed by Harveys & JMR

1–31 Dec 2025

745 hourly rows · MID-class heat meter present: yes
4.47efficiency (COP) over 745 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
742 kWh
Heat delivered
3315 kWh (heat meter)
Estimate without heat meter
flow sensor 4.60 · temperature model 3.91
Mean outdoor temperature
7.0 °C · 708 space-heating hours
Flow temperature at 0 °C outside
35.7 °C (curve slope -0.29 per K)
Flow − return while heating
2.6 K
House needs at −3 °C
6.5 kW (unit rated 10 kW) · fit r² 0.40
Hot water
no hot-water flag in data
warningOnly 2.6 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day024482025-12-01: 16.8 kWh, outside 10.3 °C2025-12-02: 19.3 kWh, outside 7.8 °C2025-12-03: 24.4 kWh, outside 5.2 °C2025-12-04: 23.8 kWh, outside 5.5 °C2025-12-05: 26.7 kWh, outside 4.9 °C2025-12-06: 16.5 kWh, outside 10 °C2025-12-07: 16.9 kWh, outside 10.8 °C2025-12-08: 14.5 kWh, outside 11.8 °C2025-12-09: 14 kWh, outside 12.7 °C2025-12-10: 18 kWh, outside 9.6 °C2025-12-11: 19.6 kWh, outside 8.6 °C2025-12-12: 18.6 kWh, outside 8.3 °C2025-12-13: 26.9 kWh, outside 4.1 °C2025-12-14: 19.3 kWh, outside 8.7 °C2025-12-15: 14.1 kWh, outside 10.5 °C2025-12-16: 20 kWh, outside 7.4 °C2025-12-17: 25 kWh, outside 5.6 °C2025-12-18: 16.8 kWh, outside 10.9 °C2025-12-19: 22.3 kWh, outside 6.9 °C2025-12-20: 21.6 kWh, outside 6.1 °C2025-12-21: 18.3 kWh, outside 9.2 °C2025-12-22: 17.1 kWh, outside 10 °C2025-12-23: 23.5 kWh, outside 6.8 °C2025-12-24: 29.7 kWh, outside 4.1 °C2025-12-25: 41.8 kWh, outside 2.7 °C2025-12-26: 35.4 kWh, outside 3.3 °C2025-12-27: 33.6 kWh, outside 4.2 °C2025-12-28: 30 kWh, outside 5.8 °C2025-12-29: 30.9 kWh, outside 4.9 °C2025-12-30: 36.2 kWh, outside 2.5 °C2025-12-31: 48.1 kWh, outside -1.6 °C2026-01-01: 1.8 kWh, outside -0.6 °Cdaily COP (heat ÷ electricity)1352025-12-01: COP 4.862025-12-02: COP 5.082025-12-03: COP 4.582025-12-04: COP 4.542025-12-05: COP 4.22025-12-06: COP 5.442025-12-07: COP 4.942025-12-08: COP 52025-12-09: COP 4.692025-12-10: COP 5.292025-12-11: COP 4.872025-12-12: COP 4.82025-12-13: COP 4.322025-12-14: COP 4.812025-12-15: COP 5.032025-12-16: COP 4.912025-12-17: COP 4.052025-12-18: COP 4.932025-12-19: COP 4.962025-12-20: COP 4.752025-12-21: COP 4.742025-12-22: COP 5.212025-12-23: COP 4.662025-12-24: COP 4.522025-12-25: COP 4.042025-12-26: COP 4.142025-12-27: COP 4.122025-12-28: COP 4.492025-12-29: COP 4.282025-12-30: COP 3.822025-12-31: COP 3.142026-01-01: COP 3.0312-0112-0512-0912-1312-1712-2112-2512-29
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-7-4-12581114outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.