745 hourly rows · MID-class heat meter present: yes
2.99efficiency (COP) over 745 hours, from the heat meter better than 8% of the metered fleet in January 2026
Electricity used
396 kWh
Heat delivered
1183 kWh (heat meter)
Estimate without heat meter
flow sensor 3.23 · temperature model 3.35
Mean outdoor temperature
8.4 °C · 144 space-heating hours
Flow temperature at 0 °C outside
44.8 °C (curve slope -0.87 per K)
Flow − return while heating
3.4 K
House needs at −3 °C
7.9 kW (unit rated 11 kW) · fit r² 0.08
Hot water
24% of electricity, COP 2.85
seriousWinter efficiency 2.99 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
noteOwner’s note on the source site: “Not main heating source or a holiday home, booster heater not metered”
valueReaching the fleet’s January median (3.69) would have saved about £19 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.