Heatproof
Home / system #382

Samsung Gen 7

Highley Nr Bridgnorth Shropshire. · Detached · 155 m² · 1940 to 1982 · 8 kW · radiators · installed by EcoWright Energy

Last 30 days

721 hourly rows · MID-class heat meter present: yes
4.95efficiency (COP) over 721 hours, from the heat meter
better than 98% of the metered fleet in January 2026
Electricity used
162 kWh
Heat delivered
800 kWh (heat meter)
Estimate without heat meter
flow sensor 5.56 · temperature model 5.09
Mean outdoor temperature
10.8 °C · 140 space-heating hours
Flow temperature at 0 °C outside
30.1 °C (curve slope 0.14 per K)
Flow − return while heating
4.7 K
House needs at −3 °C
4.9 kW (unit rated 8 kW) · fit r² 0.02
Hot water
25% of electricity, COP 4.56
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day06112026-10-08: 1.1 kWh, outside 12.1 °C2026-10-09: 1.6 kWh, outside 14.8 °C2026-10-10: 1.3 kWh, outside 11.4 °C2026-10-11: 0.9 kWh, outside 11 °C2026-10-12: 1.4 kWh, outside 15.8 °C2026-10-13: 1.2 kWh, outside 15.7 °C2026-10-14: 1.4 kWh, outside 14 °C2026-10-15: 1.2 kWh, outside 16.9 °C2026-10-16: 1.6 kWh, outside 10.8 °C2026-10-17: 6.2 kWh, outside 7.3 °C2026-10-18: 7.1 kWh, outside 9.1 °C2026-10-19: 4.1 kWh, outside 10.3 °C2026-10-20: 6.5 kWh, outside 10.1 °C2026-10-21: 6.8 kWh, outside 8.7 °C2026-10-22: 5.5 kWh, outside 10.2 °C2026-10-23: 7.3 kWh, outside 9.4 °C2026-10-24: 11.4 kWh, outside 10 °C2026-10-25: 10.5 kWh, outside 10.8 °C2026-10-26: 6.6 kWh, outside 12.3 °C2026-10-27: 3.5 kWh, outside 13.2 °C2026-10-28: 5.5 kWh, outside 11.1 °C2026-10-29: 5.3 kWh, outside 12 °C2026-10-30: 5 kWh, outside 10.4 °C2026-10-31: 7.3 kWh, outside 8.6 °C2026-11-01: 7.3 kWh, outside 8.5 °C2026-11-02: 8.2 kWh, outside 7.9 °C2026-11-03: 7.8 kWh, outside 7.5 °C2026-11-04: 7.4 kWh, outside 9.5 °C2026-11-05: 8.8 kWh, outside 8.8 °C2026-11-06: 8.4 kWh, outside 9 °C2026-11-07: 3.5 kWh, outside 5.3 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 3.452026-10-09: COP 4.322026-10-10: COP 3.042026-10-11: COP 2.062026-10-12: COP 4.92026-10-13: COP 3.962026-10-14: COP 3.662026-10-15: COP 4.392026-10-16: COP 3.232026-10-17: COP 5.112026-10-18: COP 4.882026-10-19: COP 4.922026-10-20: COP 5.362026-10-21: COP 4.972026-10-22: COP 4.952026-10-23: COP 4.952026-10-24: COP 5.252026-10-25: COP 4.972026-10-26: COP 5.362026-10-27: COP 4.82026-10-28: COP 5.052026-10-29: COP 5.262026-10-30: COP 5.152026-10-31: COP 5.022026-11-01: COP 4.982026-11-02: COP 4.862026-11-03: COP 5.042026-11-04: COP 5.062026-11-05: COP 4.922026-11-06: COP 5.052026-11-07: COP 4.9710-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.