729 hourly rows · MID-class heat meter present: yes
4.53efficiency (COP) over 729 hours, from the heat meter better than 93% of the metered fleet in January 2026
Electricity used
412 kWh
Heat delivered
1869 kWh (heat meter)
Estimate without heat meter
flow sensor 4.67 · temperature model 4.35
Mean outdoor temperature
7.4 °C · 398 space-heating hours · cooling 4 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
28.7 °C (curve slope 0.34 per K)
Flow − return while heating
4.4 K
House needs at −3 °C
3.1 kW (unit rated 8 kW) · fit r² 0.12
Hot water
15% of electricity, COP 3.66
infoUnit is rated 8 kW but the house needs about 3.1 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.