Mitsubishi Ecodan

Sheffield · Semi-detached · 136 m² · 1900 to 1939 · 11.2 kW · radiators · installed by Damon Blakemore (Repaired)

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: yes
3.83efficiency (COP) over 721 hours, from the heat meter
better than 64% of the metered fleet in January 2026
Electricity used
720 kWh
Heat delivered
2759 kWh (heat meter)
Estimate without heat meter
flow sensor 3.69 · temperature model 3.25
Mean outdoor temperature
5.2 °C · 626 space-heating hours
Flow temperature at 0 °C outside
39.6 °C (curve slope -0.56 per K)
Flow − return while heating
3.8 K
House needs at −3 °C
6.2 kW (unit rated 11.2 kW) · fit r² 0.26
Hot water
14% of electricity, COP 3.85
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
noteOwner’s note on the source site: “Not recording negative heat on heat meter”

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day021422026-01-05: 40.8 kWh, outside -0.5 °C2026-01-06: 42.1 kWh, outside 1.8 °C2026-01-07: 31.9 kWh, outside 4.2 °C2026-01-08: 40.4 kWh, outside 2.4 °C2026-01-09: 36.4 kWh, outside 3.3 °C2026-01-10: 31 kWh, outside 0.9 °C2026-01-11: 32.5 kWh, outside 4.5 °C2026-01-12: 21 kWh, outside 9 °C2026-01-13: 17.8 kWh, outside 6.9 °C2026-01-14: 27.5 kWh, outside 3.3 °C2026-01-15: 30.3 kWh, outside 6 °C2026-01-16: 22.9 kWh, outside 6.2 °C2026-01-17: 14.9 kWh, outside 7.3 °C2026-01-18: 12.7 kWh, outside 6.4 °C2026-01-19: 20.2 kWh, outside 8.2 °C2026-01-20: 13.5 kWh, outside 8.7 °C2026-01-21: 12.1 kWh, outside 7.4 °C2026-01-22: 19.4 kWh, outside 6.9 °C2026-01-23: 13.9 kWh, outside 7 °C2026-01-24: 14.3 kWh, outside 6.6 °C2026-01-25: 20.4 kWh, outside 5.3 °C2026-01-26: 28.3 kWh, outside 3.2 °C2026-01-27: 27.6 kWh, outside 5.4 °C2026-01-28: 15.4 kWh, outside 4.8 °C2026-01-29: 24.4 kWh, outside 4.1 °C2026-01-30: 20.3 kWh, outside 4.4 °C2026-01-31: 18.5 kWh, outside 7.3 °C2026-02-01: 16.2 kWh, outside 7.1 °C2026-02-02: 20.7 kWh, outside 6.1 °C2026-02-03: 31.4 kWh, outside 3.1 °C2026-02-04: 1.2 kWh, outside 1.5 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 3.272026-01-06: COP 3.372026-01-07: COP 3.62026-01-08: COP 3.42026-01-09: COP 3.512026-01-10: COP 3.342026-01-11: COP 3.742026-01-12: COP 4.442026-01-13: COP 4.052026-01-14: COP 3.572026-01-15: COP 3.952026-01-16: COP 3.962026-01-17: COP 4.382026-01-18: COP 4.322026-01-19: COP 4.382026-01-20: COP 4.452026-01-21: COP 4.572026-01-22: COP 4.382026-01-23: COP 4.452026-01-24: COP 4.252026-01-25: COP 4.092026-01-26: COP 3.662026-01-27: COP 4.022026-01-28: COP 4.012026-01-29: COP 3.712026-01-30: COP 3.622026-01-31: COP 4.242026-02-01: COP 4.232026-02-02: COP 4.062026-02-03: COP 3.612026-02-04: COP 3.5201-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-4-20246810outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.