Home / system #525
MasterTherm BA221
Lincolnshire · Bungalow · 80 m² · 1940 to 1982 · 7.7 kW · underfloor · installed by Andy Brown
Last 7 days
169 hourly rows · MID-class heat meter present: yes
4.15efficiency (COP) over 169 hours, from the heat meter
better than 84% of the metered fleet in January 2026
better than 84% of the metered fleet in January 2026
- Electricity used
- 73 kWh
- Heat delivered
- 303 kWh (heat meter)
- Estimate without heat meter
- flow sensor 4.10 · temperature model 4.85
- Mean outdoor temperature
- 10.2 °C · 78 space-heating hours · cooling 1 kWh removed (0 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 30.3 °C (curve slope -0.06 per K)
- Flow − return while heating
- 3.1 K
- House needs at −3 °C
- 3.4 kW (unit rated 7.7 kW) · fit r² 0.00
- Hot water
- 30% of electricity, COP 2.94
infoUnit is rated 7.7 kW but the house needs about 3.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C