Heatproof
Home / system #539

Vaillant Arotherm+

Great Bedwyn, Wiltshire · Semi-detached · 117 m² · 1940 to 1982 · 7 kW · underfloor · installed by Ramsbury Electrical

Last 7 days

169 hourly rows · MID-class heat meter present: yes
4.50efficiency (COP) over 169 hours, from the heat meter
better than 93% of the metered fleet in January 2026
Electricity used
81 kWh
Heat delivered
362 kWh (heat meter)
Estimate without heat meter
flow sensor 0.00 · temperature model –
Mean outdoor temperature
– °C · 152 space-heating hours
Flow temperature at 0 °C outside
–
Flow − return while heating
1.6 K
House needs at −3 °C
–
Hot water
24% of electricity, COP 3.58
warningOnly 1.6 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day06132026-10-31: 5.6 kWh, outside – °C2026-11-01: 11.8 kWh, outside – °C2026-11-02: 11.2 kWh, outside – °C2026-11-03: 11.4 kWh, outside – °C2026-11-04: 12.1 kWh, outside – °C2026-11-05: 12.5 kWh, outside – °C2026-11-06: 11 kWh, outside – °C2026-11-07: 4.9 kWh, outside – °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.612026-11-01: COP 4.432026-11-02: COP 4.62026-11-03: COP 4.52026-11-04: COP 4.532026-11-05: COP 4.522026-11-06: COP 4.562026-11-07: COP 4.0210-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.