Heatproof
Home / system #585

Vaillant Arotherm+

Hinstock, Shropshire · Detached · 200 m² · 1983 to 2011 · 7 kW · radiators · installed by RG Plumbing Services

Last 7 days

169 hourly rows · MID-class heat meter present: yes
4.34efficiency (COP) over 169 hours, from the heat meter
better than 91% of the metered fleet in January 2026
Electricity used
120 kWh
Heat delivered
520 kWh (heat meter)
Estimate without heat meter
flow sensor 4.31 · temperature model 3.92
Mean outdoor temperature
8.0 °C · 124 space-heating hours
Flow temperature at 0 °C outside
34.0 °C (curve slope -0.34 per K)
Flow − return while heating
2.8 K
House needs at −3 °C
4.6 kW (unit rated 7 kW) · fit r² 0.06
Hot water
33% of electricity, COP 3.03
warningOnly 2.8 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 33% of electricity at COP 3.03
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day010202026-10-31: 12 kWh, outside 8.5 °C2026-11-01: 19.8 kWh, outside 7.5 °C2026-11-02: 18 kWh, outside 6.6 °C2026-11-03: 13.7 kWh, outside 8.3 °C2026-11-04: 15.8 kWh, outside 9 °C2026-11-05: 15.9 kWh, outside 8.4 °C2026-11-06: 15.2 kWh, outside 8.6 °C2026-11-07: 9.6 kWh, outside 6 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.662026-11-01: COP 4.082026-11-02: COP 4.152026-11-03: COP 4.562026-11-04: COP 4.492026-11-05: COP 4.672026-11-06: COP 4.542026-11-07: COP 3.3710-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060135791113outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.