Home / system #593
Daikin Altherma 3
Wing, Beds · Detached · 140 m² · 2012 or newer · 5 kW · radiators · installed by Self-install
5 Jan – 4 Feb 2026 (winter reference)
202 hourly rows · MID-class heat meter present: yes
3.12efficiency (COP) over 202 hours, from the heat meter
better than 17% of the metered fleet in January 2026
better than 17% of the metered fleet in January 2026
- Electricity used
- 108 kWh
- Heat delivered
- 338 kWh (heat meter)
- Estimate without heat meter
- flow sensor 3.02 · temperature model 3.54
- Mean outdoor temperature
- 4.3 °C · 200 space-heating hours
- Flow temperature at 0 °C outside
- 38.4 °C (curve slope -1.00 per K)
- Flow − return while heating
- 2.3 K
- House needs at −3 °C
- 2.8 kW (unit rated 5 kW) · fit r² 0.55
- Hot water
- no hot-water flag in data
warningOnly 2.3 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
valueReaching the fleet’s January median (3.69) would have saved about £4 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.