Home / system #620
Vaillant Arotherm+
Oxford, Oxfordshire · Semi-detached · 100 m² · 1900 to 1939 · 5 kW · radiators · installed by Boxt
Last 7 days
169 hourly rows · MID-class heat meter present: yes
4.02efficiency (COP) over 169 hours, from the heat meter
better than 77% of the metered fleet in January 2026
better than 77% of the metered fleet in January 2026
- Electricity used
- 47 kWh
- Heat delivered
- 189 kWh (heat meter)
- Estimate without heat meter
- flow sensor 3.59 · temperature model 4.52
- Mean outdoor temperature
- 8.3 °C · 96 space-heating hours
- Flow temperature at 0 °C outside
- 34.5 °C (curve slope -0.66 per K)
- Flow − return while heating
- 1.3 K
- House needs at −3 °C
- 2.0 kW (unit rated 5 kW) · fit r² 0.20
- Hot water
- 27% of electricity, COP 3.43
warningOnly 1.3 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
infoUnit is rated 5 kW but the house needs about 2 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Not recording negative heat on heat meter”
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.