Heatproof
Home / system #652

Vaillant Arotherm+

Milton Keynes, Buckinghamshire · Detached · 149 m² · 1983 to 2011 · 7 kW · underfloor · installed by Custom Renewables

1–31 Dec 2025

744 hourly rows · MID-class heat meter present: yes
3.90efficiency (COP) over 744 hours, from the heat meter
better than 66% of the metered fleet in January 2026
Electricity used
485 kWh
Heat delivered
1890 kWh (heat meter)
Estimate without heat meter
flow sensor 3.88 · temperature model 3.94
Mean outdoor temperature
7.0 °C · 369 space-heating hours · cooling 1 kWh removed (1 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
33.0 °C (curve slope -0.30 per K)
Flow − return while heating
2.8 K
House needs at −3 °C
5.1 kW (unit rated 7 kW) · fit r² 0.04
Hot water
25% of electricity, COP 3.62
warningOnly 2.8 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day013262025-12-01: 19.3 kWh, outside 9.9 °C2025-12-02: 14.1 kWh, outside 8.1 °C2025-12-03: 20.9 kWh, outside 5.2 °C2025-12-04: 18.3 kWh, outside 6.1 °C2025-12-05: 23.6 kWh, outside 4.7 °C2025-12-06: 17 kWh, outside 9.8 °C2025-12-07: 12.1 kWh, outside 10.1 °C2025-12-08: 9.7 kWh, outside 11.4 °C2025-12-09: 10.3 kWh, outside 12.5 °C2025-12-10: 13.3 kWh, outside 10 °C2025-12-11: 12.9 kWh, outside 8.9 °C2025-12-12: 12.8 kWh, outside 9 °C2025-12-13: 18.9 kWh, outside 5.6 °C2025-12-14: 22.9 kWh, outside 8.6 °C2025-12-15: 8.1 kWh, outside 10.3 °C2025-12-16: 11.3 kWh, outside 7.6 °C2025-12-17: 13.5 kWh, outside 5.4 °C2025-12-18: 7.9 kWh, outside 10.5 °C2025-12-19: 10.7 kWh, outside 7.4 °C2025-12-20: 14.1 kWh, outside 5 °C2025-12-21: 10.7 kWh, outside 8.5 °C2025-12-22: 11 kWh, outside 8.4 °C2025-12-23: 13.2 kWh, outside 5.9 °C2025-12-24: 18.7 kWh, outside 4 °C2025-12-25: 22.2 kWh, outside 2.8 °C2025-12-26: 20.9 kWh, outside 3.1 °C2025-12-27: 19.5 kWh, outside 3.9 °C2025-12-28: 14.6 kWh, outside 5.4 °C2025-12-29: 17.8 kWh, outside 5.1 °C2025-12-30: 18.9 kWh, outside 3.6 °C2025-12-31: 26 kWh, outside 0.8 °C2026-01-01: 0 kWh, outside 0.9 °Cdaily COP (heat ÷ electricity)1352025-12-01: COP 3.62025-12-02: COP 3.662025-12-03: COP 32025-12-04: COP 3.42025-12-05: COP 3.262025-12-06: COP 3.892025-12-07: COP 4.42025-12-08: COP 4.462025-12-09: COP 4.112025-12-10: COP 3.92025-12-11: COP 3.952025-12-12: COP 3.952025-12-13: COP 3.022025-12-14: COP 3.442025-12-15: COP 5.152025-12-16: COP 4.832025-12-17: COP 4.342025-12-18: COP 5.612025-12-19: COP 4.752025-12-20: COP 4.422025-12-21: COP 4.962025-12-22: COP 4.792025-12-23: COP 4.512025-12-24: COP 3.742025-12-25: COP 3.852025-12-26: COP 3.732025-12-27: COP 3.952025-12-28: COP 4.182025-12-29: COP 3.842025-12-30: COP 3.642025-12-31: COP 3.2412-0112-0512-0912-1312-1712-2112-2512-29
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-3-113579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.