Home / system #670

Vaillant Arotherm+

Yelverton, Devon · Bungalow · 166 m² · 1940 to 1982 · 7 kW · radiators · installed by Reco Energy

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: yes
4.43efficiency (COP) over 721 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
815 kWh
Heat delivered
3610 kWh (heat meter)
Estimate without heat meter
flow sensor 4.47 · temperature model 3.86
Mean outdoor temperature
7.7 °C · 663 space-heating hours
Flow temperature at 0 °C outside
38.5 °C (curve slope -0.51 per K)
Flow − return while heating
4.9 K
House needs at −3 °C
7.0 kW (unit rated 7 kW) · fit r² 0.47
Hot water
10% of electricity, COP 3.69
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day025502026-01-05: 50 kWh, outside 2 °C2026-01-06: 44.8 kWh, outside 3.2 °C2026-01-07: 25.4 kWh, outside 7.7 °C2026-01-08: 28.4 kWh, outside 7.6 °C2026-01-09: 38.7 kWh, outside 6.2 °C2026-01-10: 41.3 kWh, outside 4.9 °C2026-01-11: 20.8 kWh, outside 10.6 °C2026-01-12: 16.6 kWh, outside 11 °C2026-01-13: 19.4 kWh, outside 9.6 °C2026-01-14: 31.7 kWh, outside 5.1 °C2026-01-15: 21.8 kWh, outside 8.1 °C2026-01-16: 25.1 kWh, outside 7.9 °C2026-01-17: 25.9 kWh, outside 7.9 °C2026-01-18: 23.4 kWh, outside 6.7 °C2026-01-19: 26.8 kWh, outside 6.8 °C2026-01-20: 25.6 kWh, outside 7.8 °C2026-01-21: 21.7 kWh, outside 9.7 °C2026-01-22: 22.1 kWh, outside 8 °C2026-01-23: 27.1 kWh, outside 8.2 °C2026-01-24: 25.6 kWh, outside 9 °C2026-01-25: 26.5 kWh, outside 7.2 °C2026-01-26: 25 kWh, outside 8 °C2026-01-27: 22.6 kWh, outside 9.3 °C2026-01-28: 28.2 kWh, outside 7.3 °C2026-01-29: 23 kWh, outside 8.9 °C2026-01-30: 25.9 kWh, outside 8.5 °C2026-01-31: 23.9 kWh, outside 8.9 °C2026-02-01: 26.2 kWh, outside 7.3 °C2026-02-02: 30.3 kWh, outside 6.4 °C2026-02-03: 20.5 kWh, outside 9.8 °C2026-02-04: 0.9 kWh, outside 9.3 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 2.862026-01-06: COP 2.932026-01-07: COP 4.662026-01-08: COP 4.52026-01-09: COP 3.652026-01-10: COP 3.312026-01-11: COP 5.242026-01-12: COP 5.632026-01-13: COP 5.332026-01-14: COP 3.992026-01-15: COP 5.12026-01-16: COP 4.742026-01-17: COP 4.712026-01-18: COP 4.882026-01-19: COP 4.472026-01-20: COP 4.762026-01-21: COP 5.152026-01-22: COP 5.032026-01-23: COP 4.662026-01-24: COP 4.882026-01-25: COP 4.632026-01-26: COP 4.862026-01-27: COP 4.872026-01-28: COP 4.332026-01-29: COP 5.042026-01-30: COP 4.852026-01-31: COP 4.972026-02-01: COP 4.452026-02-02: COP 4.242026-02-03: COP 5.362026-02-04: COP 5.1701-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-4-202468101214outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.