Heatproof
Home / system #685

Octopus Cosy

Pudsey, Leeds · Detached · 215 m² · 2012 or newer · 9 kW · radiators · installed by Octopus Energy Services

Last 7 days

169 hourly rows · MID-class heat meter present: yes
4.03efficiency (COP) over 169 hours, from the heat meter
better than 79% of the metered fleet in January 2026
Electricity used
74 kWh
Heat delivered
300 kWh (heat meter)
Estimate without heat meter
flow sensor 3.48 · temperature model 3.99
Mean outdoor temperature
9.4 °C · 35 space-heating hours
Flow temperature at 0 °C outside
35.7 °C (curve slope -0.50 per K)
Flow − return while heating
3.0 K
House needs at −3 °C
5.4 kW (unit rated 9 kW) · fit r² 0.01
Hot water
60% of electricity, COP 3.69
infoOnly 35 space-heating hours in this window
Space-heating findings need at least 60 hours with the compressor running below 15 °C outside. Choose a winter window or come back during the heating season.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day07132026-10-31: 3.4 kWh, outside 9.6 °C2026-11-01: 11.1 kWh, outside 7.9 °C2026-11-02: 12.6 kWh, outside 8.8 °C2026-11-03: 10.4 kWh, outside 10 °C2026-11-04: 6.8 kWh, outside 10.2 °C2026-11-05: 13.1 kWh, outside 9.9 °C2026-11-06: 10.5 kWh, outside 10 °C2026-11-07: 6.5 kWh, outside 8.3 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.052026-11-01: COP 3.692026-11-02: COP 3.542026-11-03: COP 4.252026-11-04: COP 3.982026-11-05: COP 4.392026-11-06: COP 4.282026-11-07: COP 4.1110-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.