Heatproof
Home / system #723

Samsung Gen 7

Wymondham, Norfolk · Detached · 375 m² · Pre-1900 · 16 kW · radiators · installed by Simon Bennett (Self Install)

1–31 Dec 2025

745 hourly rows · MID-class heat meter present: yes
4.45efficiency (COP) over 745 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
1106 kWh
Heat delivered
4917 kWh (heat meter)
Estimate without heat meter
flow sensor 4.50 · temperature model 3.94
Mean outdoor temperature
7.0 °C · 632 space-heating hours · cooling 1 kWh removed (1 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
37.1 °C (curve slope -0.56 per K)
Flow − return while heating
4.2 K
House needs at −3 °C
8.9 kW (unit rated 16 kW) · fit r² 0.18
Hot water
18% of electricity, COP 3.89
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day025512025-12-01: 33.7 kWh, outside 8.5 °C2025-12-02: 30.9 kWh, outside 8.1 °C2025-12-03: 40.5 kWh, outside 5.3 °C2025-12-04: 40.9 kWh, outside 6.3 °C2025-12-05: 45.1 kWh, outside 4.3 °C2025-12-06: 35.8 kWh, outside 9.3 °C2025-12-07: 32 kWh, outside 9.2 °C2025-12-08: 26.7 kWh, outside 10.3 °C2025-12-09: 21.7 kWh, outside 12 °C2025-12-10: 25.8 kWh, outside 9.6 °C2025-12-11: 27.6 kWh, outside 8.3 °C2025-12-12: 24.3 kWh, outside 9.3 °C2025-12-13: 36.5 kWh, outside 4.9 °C2025-12-14: 29.9 kWh, outside 7 °C2025-12-15: 27.9 kWh, outside 9.3 °C2025-12-16: 26.5 kWh, outside 9.1 °C2025-12-17: 38.1 kWh, outside 5.7 °C2025-12-18: 25.6 kWh, outside 10 °C2025-12-19: 31.8 kWh, outside 7.1 °C2025-12-20: 39.8 kWh, outside 5.4 °C2025-12-21: 27.3 kWh, outside 9.1 °C2025-12-22: 31.4 kWh, outside 7.6 °C2025-12-23: 36.5 kWh, outside 6.3 °C2025-12-24: 46.5 kWh, outside 4.8 °C2025-12-25: 42.5 kWh, outside 4.4 °C2025-12-26: 50.9 kWh, outside 4 °C2025-12-27: 47.1 kWh, outside 5.8 °C2025-12-28: 38.5 kWh, outside 6.5 °C2025-12-29: 46.1 kWh, outside 5.9 °C2025-12-30: 46.2 kWh, outside 3.4 °C2025-12-31: 50.3 kWh, outside 1.3 °C2026-01-01: 2.3 kWh, outside 0.5 °Cdaily COP (heat ÷ electricity)1352025-12-01: COP 4.992025-12-02: COP 5.062025-12-03: COP 4.422025-12-04: COP 4.582025-12-05: COP 3.852025-12-06: COP 4.852025-12-07: COP 4.942025-12-08: COP 5.162025-12-09: COP 5.542025-12-10: COP 5.082025-12-11: COP 5.182025-12-12: COP 5.642025-12-13: COP 4.262025-12-14: COP 4.832025-12-15: COP 5.192025-12-16: COP 5.142025-12-17: COP 4.112025-12-18: COP 5.52025-12-19: COP 4.732025-12-20: COP 4.312025-12-21: COP 5.42025-12-22: COP 4.862025-12-23: COP 4.572025-12-24: COP 3.862025-12-25: COP 3.792025-12-26: COP 3.682025-12-27: COP 4.092025-12-28: COP 4.142025-12-29: COP 4.12025-12-30: COP 3.482025-12-31: COP 2.92026-01-01: COP 3.112-0112-0512-0912-1312-1712-2112-2512-29
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-113579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.