Heatproof
Home / system #759

Vaillant Arotherm+

Tavistock · Mid-terrace · 162 m² · Pre-1900 · 7 kW · radiators · installed by Reco Energy

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: yes
4.54efficiency (COP) over 721 hours, from the heat meter
better than 94% of the metered fleet in January 2026
Electricity used
571 kWh
Heat delivered
2590 kWh (heat meter)
Estimate without heat meter
flow sensor 4.51 · temperature model 3.79
Mean outdoor temperature
5.6 °C · 679 space-heating hours
Flow temperature at 0 °C outside
35.0 °C (curve slope -0.43 per K)
Flow − return while heating
2.5 K
House needs at −3 °C
4.7 kW (unit rated 7 kW) · fit r² 0.34
Hot water
10% of electricity, COP 3.74
warningOnly 2.5 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day019382026-01-05: 37.7 kWh, outside -0.7 °C2026-01-06: 33.4 kWh, outside -0.3 °C2026-01-07: 17.9 kWh, outside 4.1 °C2026-01-08: 17.6 kWh, outside 5.3 °C2026-01-09: 21.7 kWh, outside 3.8 °C2026-01-10: 29.1 kWh, outside 2.2 °C2026-01-11: 17.3 kWh, outside 8.1 °C2026-01-12: 14.9 kWh, outside 9.5 °C2026-01-13: 15.5 kWh, outside 8.7 °C2026-01-14: 23.7 kWh, outside 4 °C2026-01-15: 15.9 kWh, outside 6.6 °C2026-01-16: 18.1 kWh, outside 5 °C2026-01-17: 16.9 kWh, outside 5.2 °C2026-01-18: 17.6 kWh, outside 5.4 °C2026-01-19: 19.2 kWh, outside 4.3 °C2026-01-20: 17.3 kWh, outside 5.7 °C2026-01-21: 15.5 kWh, outside 7.4 °C2026-01-22: 15 kWh, outside 6.9 °C2026-01-23: 18.5 kWh, outside 6.2 °C2026-01-24: 17.7 kWh, outside 7.1 °C2026-01-25: 19.5 kWh, outside 5.8 °C2026-01-26: 17.6 kWh, outside 6.8 °C2026-01-27: 13.4 kWh, outside 7.7 °C2026-01-28: 19 kWh, outside 5.2 °C2026-01-29: 13.5 kWh, outside 7 °C2026-01-30: 16.6 kWh, outside 6.6 °C2026-01-31: 16 kWh, outside 5.5 °C2026-02-01: 18.2 kWh, outside 5.8 °C2026-02-02: 18.1 kWh, outside 5.5 °C2026-02-03: 17.5 kWh, outside 8 °C2026-02-04: 0.7 kWh, outside 6.7 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 32026-01-06: COP 3.262026-01-07: COP 4.92026-01-08: COP 4.882026-01-09: COP 4.342026-01-10: COP 3.622026-01-11: COP 5.252026-01-12: COP 5.352026-01-13: COP 5.22026-01-14: COP 3.812026-01-15: COP 4.992026-01-16: COP 4.472026-01-17: COP 4.792026-01-18: COP 4.822026-01-19: COP 4.262026-01-20: COP 4.832026-01-21: COP 4.992026-01-22: COP 5.162026-01-23: COP 4.772026-01-24: COP 5.182026-01-25: COP 4.92026-01-26: COP 4.812026-01-27: COP 5.162026-01-28: COP 4.462026-01-29: COP 5.232026-01-30: COP 4.752026-01-31: COP 5.032026-02-01: COP 4.652026-02-02: COP 4.652026-02-03: COP 5.162026-02-04: COP 5.1501-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-6-4-2024681012outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.