Home / system #78
Vaillant Arotherm+
Bishops Stortford · Detached · 156 m² · 1940 to 1982 · 5 kW · underfloor · installed by Pro-Flo
Last 7 days
169 hourly rows · MID-class heat meter present: yes
4.38efficiency (COP) over 169 hours, from the heat meter
better than 92% of the metered fleet in January 2026
better than 92% of the metered fleet in January 2026
- Electricity used
- 46 kWh
- Heat delivered
- 200 kWh (heat meter)
- Estimate without heat meter
- flow sensor 4.51 · temperature model 4.66
- Mean outdoor temperature
- 10.1 °C · 68 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 33.4 °C (curve slope -0.06 per K)
- Flow − return while heating
- 4.2 K
- House needs at −3 °C
- 7.9 kW (unit rated 5 kW) · fit r² 0.09
- Hot water
- no hot-water flag in data
warningUnit is rated 5 kW but the house needs about 7.9 kW at −3 °C
Expect backup heater use on the coldest days. Improve insulation or draught-proofing before adding capacity.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.