Heatproof
Home / system #909

Vaillant Arotherm+

Wetherby, West Yorkshire · Detached · 100 m² · 1983 to 2011 · 7 kW · radiators · installed by Clear Skies Energy Ltd

Last 30 days

721 hourly rows · MID-class heat meter present: yes
4.47efficiency (COP) over 721 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
320 kWh
Heat delivered
1431 kWh (heat meter)
Estimate without heat meter
flow sensor 4.24 · temperature model 4.76
Mean outdoor temperature
10.5 °C · 412 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
37.3 °C (curve slope -0.66 per K)
Flow − return while heating
2.0 K
House needs at −3 °C
5.3 kW (unit rated 7 kW) · fit r² 0.14
Hot water
21% of electricity, COP 3.46
warningOnly 2 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day010212026-10-08: 5.7 kWh, outside 11.3 °C2026-10-09: 5.7 kWh, outside 13.6 °C2026-10-10: 8.8 kWh, outside 10.8 °C2026-10-11: 13.8 kWh, outside 9.6 °C2026-10-12: 8.4 kWh, outside 11.6 °C2026-10-13: 3.6 kWh, outside 14.6 °C2026-10-14: 7.2 kWh, outside 12.9 °C2026-10-15: 3.7 kWh, outside 15 °C2026-10-16: 8.2 kWh, outside 9.8 °C2026-10-17: 12.9 kWh, outside 8.2 °C2026-10-18: 14.3 kWh, outside 9.1 °C2026-10-19: 7.7 kWh, outside 12.3 °C2026-10-20: 8.1 kWh, outside 11.5 °C2026-10-21: 10.3 kWh, outside 9.7 °C2026-10-22: 12.7 kWh, outside 8.3 °C2026-10-23: 10.2 kWh, outside 9.7 °C2026-10-24: 17.1 kWh, outside 8.8 °C2026-10-25: 15.6 kWh, outside 10.4 °C2026-10-26: 11.3 kWh, outside 11.2 °C2026-10-27: 9.5 kWh, outside 13.1 °C2026-10-28: 9.7 kWh, outside 11.1 °C2026-10-29: 8.8 kWh, outside 10.5 °C2026-10-30: 10 kWh, outside 9.6 °C2026-10-31: 12.3 kWh, outside 8.6 °C2026-11-01: 20.7 kWh, outside 7.5 °C2026-11-02: 15.3 kWh, outside 7.9 °C2026-11-03: 11.6 kWh, outside 9.2 °C2026-11-04: 9.5 kWh, outside 9.7 °C2026-11-05: 11.9 kWh, outside 9.9 °C2026-11-06: 10.8 kWh, outside 9.6 °C2026-11-07: 4.5 kWh, outside 7.9 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 4.752026-10-09: COP 5.082026-10-10: COP 4.552026-10-11: COP 3.712026-10-12: COP 4.822026-10-13: COP 4.812026-10-14: COP 4.342026-10-15: COP 5.122026-10-16: COP 4.582026-10-17: COP 4.242026-10-18: COP 4.012026-10-19: COP 4.92026-10-20: COP 4.942026-10-21: COP 4.752026-10-22: COP 4.322026-10-23: COP 4.662026-10-24: COP 4.272026-10-25: COP 3.942026-10-26: COP 4.82026-10-27: COP 4.592026-10-28: COP 4.852026-10-29: COP 4.732026-10-30: COP 4.762026-10-31: COP 4.472026-11-01: COP 3.892026-11-02: COP 4.412026-11-03: COP 4.652026-11-04: COP 4.742026-11-05: COP 4.592026-11-06: COP 4.82026-11-07: COP 4.0110-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.