Home / system #1086

Heliotherm Comfort Compact

Richmond · Detached · 630 m² · 1900 to 1939 · 18 kW · underfloor · installed by Urban Plumbers Ltd

Last 30 days

426 hourly rows · MID-class heat meter present: yes
4.80efficiency (COP) over 426 hours, from the heat meter
better than 98% of the metered fleet in January 2026
Electricity used
512 kWh
Heat delivered
2461 kWh (heat meter)
Estimate without heat meter
flow sensor 4.95 · temperature model 5.35
Mean outdoor temperature
10.5 °C · 266 space-heating hours · cooling 8 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
29.0 °C (curve slope 0.04 per K)
Flow − return while heating
3.6 K
House needs at −3 °C
9.9 kW (unit rated 18 kW) · fit r² 0.00
Hot water
no hot-water flag in data
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day023462026-10-20: 10.1 kWh, outside 10.6 °C2026-10-21: 45.5 kWh, outside 9.1 °C2026-10-22: 26.1 kWh, outside 12 °C2026-10-23: 37.4 kWh, outside 10.5 °C2026-10-24: 30.7 kWh, outside 10.4 °C2026-10-25: 38 kWh, outside 11.1 °C2026-10-26: 20 kWh, outside 12.4 °C2026-10-27: 20.5 kWh, outside 13.9 °C2026-10-28: 21.9 kWh, outside 11.5 °C2026-10-29: 17.3 kWh, outside 12.7 °C2026-10-30: 21 kWh, outside 10.9 °C2026-10-31: 25.4 kWh, outside 10.5 °C2026-11-01: 24.8 kWh, outside 8.8 °C2026-11-02: 27.1 kWh, outside 9.8 °C2026-11-03: 29.3 kWh, outside 9.9 °C2026-11-04: 33.3 kWh, outside 9.5 °C2026-11-05: 33 kWh, outside 9.2 °C2026-11-06: 34.1 kWh, outside 8.3 °C2026-11-07: 18.5 kWh, outside 4.5 °Cdaily COP (heat ÷ electricity)1352026-10-20: COP 5.132026-10-21: COP 4.72026-10-22: COP 5.152026-10-23: COP 4.752026-10-24: COP 4.292026-10-25: COP 4.82026-10-26: COP 4.72026-10-27: COP 4.912026-10-28: COP 4.742026-10-29: COP 5.252026-10-30: COP 5.492026-10-31: COP 4.872026-11-01: COP 4.92026-11-02: COP 4.742026-11-03: COP 4.732026-11-04: COP 4.772026-11-05: COP 4.742026-11-06: COP 4.652026-11-07: COP 3.8110-2010-2210-2410-2610-2810-3011-0111-0311-0511-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050603579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.