427 hourly rows · MID-class heat meter present: yes
4.80efficiency (COP) over 427 hours, from the heat meter better than 98% of the metered fleet in January 2026
Electricity used
515 kWh
Heat delivered
2473 kWh (heat meter)
Estimate without heat meter
flow sensor 4.95 · temperature model 5.34
Mean outdoor temperature
10.5 °C · 267 space-heating hours · cooling 8 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
29.1 °C (curve slope 0.04 per K)
Flow − return while heating
3.6 K
House needs at −3 °C
10.1 kW (unit rated 18 kW) · fit r² 0.00
Hot water
no hot-water flag in data
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.