Home / system #112

Mitsubishi Ecodan

Rayleigh, Essex · Detached · 112 m² · 1940 to 1982 · 8.5 kW · underfloor

Last 30 days

720 hourly rows · MID-class heat meter present: no
4.69efficiency (COP) over 720 hours, from the heat meter
better than 95% of the metered fleet in January 2026
Electricity used
124 kWh
Heat delivered
579 kWh (heat meter)
Estimate without heat meter
flow sensor 7.91 · temperature model 4.72
Mean outdoor temperature
11.5 °C · 135 space-heating hours
Flow temperature at 0 °C outside
33.4 °C (curve slope -0.05 per K)
Flow − return while heating
5.1 K
House needs at −3 °C
4.1 kW (unit rated 8.5 kW) · fit r² 0.00
Hot water
no hot-water flag in data
infoUnit is rated 8.5 kW but the house needs about 4.1 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day08162026-10-08: 9.1 kWh, outside 11.2 °C2026-10-09: 4.1 kWh, outside 15.4 °C2026-10-10: 3.8 kWh, outside 11.9 °C2026-10-11: 0.3 kWh, outside 11.6 °C2026-10-12: 0.4 kWh, outside 14.5 °C2026-10-13: 0.3 kWh, outside 17.1 °C2026-10-14: 0.3 kWh, outside 14.2 °C2026-10-15: 0.3 kWh, outside 16.7 °C2026-10-16: 0.3 kWh, outside 12.8 °C2026-10-17: 0.3 kWh, outside 9.4 °C2026-10-18: 0.3 kWh, outside 9.5 °C2026-10-19: 0.3 kWh, outside 11.1 °C2026-10-20: 0.3 kWh, outside 12.4 °C2026-10-21: 0.3 kWh, outside 9.8 °C2026-10-22: 0.3 kWh, outside 10.9 °C2026-10-23: 0.3 kWh, outside 10.7 °C2026-10-24: 0.3 kWh, outside 9.8 °C2026-10-25: 0.3 kWh, outside 10.5 °C2026-10-26: 0.3 kWh, outside 11.6 °C2026-10-27: 0.3 kWh, outside 13.8 °C2026-10-28: 0.3 kWh, outside 11.1 °C2026-10-29: 2.3 kWh, outside 12.6 °C2026-10-30: 7.8 kWh, outside 10.4 °C2026-10-31: 8.7 kWh, outside 9.5 °C2026-11-01: 16.2 kWh, outside 8.9 °C2026-11-02: 14.3 kWh, outside 9.4 °C2026-11-03: 10.8 kWh, outside 9.6 °C2026-11-04: 12.1 kWh, outside 9.7 °C2026-11-05: 13.3 kWh, outside 9.8 °C2026-11-06: 11.1 kWh, outside 9.7 °C2026-11-07: 4.7 kWh, outside 6.7 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 52026-10-09: COP 5.422026-10-10: COP 4.272026-10-29: COP 6.062026-10-30: COP 5.492026-10-31: COP 5.432026-11-01: COP 4.522026-11-02: COP 4.862026-11-03: COP 4.742026-11-04: COP 4.722026-11-05: COP 4.882026-11-06: COP 4.942026-11-07: COP 4.3210-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050605678910111213141516outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.