Heatproof
Home / system #112

Mitsubishi Ecodan

Rayleigh, Essex · Detached · 112 m² · 1940 to 1982 · 8.5 kW · underfloor

Last 7 days

168 hourly rows · MID-class heat meter present: no
4.78efficiency (COP) over 168 hours, from the heat meter
better than 98% of the metered fleet in January 2026
Electricity used
87 kWh
Heat delivered
417 kWh (heat meter)
Estimate without heat meter
flow sensor 8.58 · temperature model 4.45
Mean outdoor temperature
9.4 °C · 103 space-heating hours
Flow temperature at 0 °C outside
38.0 °C (curve slope -0.48 per K)
Flow − return while heating
5.1 K
House needs at −3 °C
6.9 kW (unit rated 8.5 kW) · fit r² 0.03
Hot water
no hot-water flag in data
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day08162026-10-31: 4.6 kWh, outside 10 °C2026-11-01: 16.2 kWh, outside 8.9 °C2026-11-02: 14.3 kWh, outside 9.4 °C2026-11-03: 10.8 kWh, outside 9.6 °C2026-11-04: 12.1 kWh, outside 9.7 °C2026-11-05: 13.3 kWh, outside 9.8 °C2026-11-06: 11.1 kWh, outside 9.7 °C2026-11-07: 4.7 kWh, outside 6.7 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 5.532026-11-01: COP 4.522026-11-02: COP 4.862026-11-03: COP 4.742026-11-04: COP 4.722026-11-05: COP 4.882026-11-06: COP 4.942026-11-07: COP 4.3210-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050605678910111213outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.