Home / system #1248

Global Energy R290

Lancashire · Detached · 190 m² · Pre-1900 · 12 kW · radiators · installed by Adam Rowlandson

Last 30 days

721 hourly rows · MID-class heat meter present: yes
4.06efficiency (COP) over 721 hours, from the heat meter
better than 81% of the metered fleet in January 2026
Electricity used
757 kWh
Heat delivered
3073 kWh (heat meter)
Estimate without heat meter
flow sensor 4.22 · temperature model 4.18
Mean outdoor temperature
10.3 °C · 534 space-heating hours
Flow temperature at 0 °C outside
42.3 °C (curve slope -0.68 per K)
Flow − return while heating
2.8 K
House needs at −3 °C
6.9 kW (unit rated 12 kW) · fit r² 0.25
Hot water
23% of electricity, COP 3.94
warningOnly 2.8 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day019372026-10-08: 12.2 kWh, outside 11.2 °C2026-10-09: 13.2 kWh, outside 13.7 °C2026-10-10: 20.1 kWh, outside 11.1 °C2026-10-11: 18.4 kWh, outside 10.6 °C2026-10-12: 14.3 kWh, outside 14.5 °C2026-10-13: 14.7 kWh, outside 14.4 °C2026-10-14: 18.2 kWh, outside 13.5 °C2026-10-15: 13.4 kWh, outside 13.9 °C2026-10-16: 22.4 kWh, outside 9.2 °C2026-10-17: 27.2 kWh, outside 6.8 °C2026-10-18: 26.6 kWh, outside 8.5 °C2026-10-19: 19.7 kWh, outside 11.6 °C2026-10-20: 21.7 kWh, outside 11 °C2026-10-21: 27.3 kWh, outside 8.8 °C2026-10-22: 31.3 kWh, outside 8.5 °C2026-10-23: 37.1 kWh, outside 8.3 °C2026-10-24: 36.9 kWh, outside 9.1 °C2026-10-25: 35.8 kWh, outside 10.8 °C2026-10-26: 25.7 kWh, outside 11.8 °C2026-10-27: 23.4 kWh, outside 12.5 °C2026-10-28: 24.6 kWh, outside 11.3 °C2026-10-29: 23.8 kWh, outside 11.8 °C2026-10-30: 25.1 kWh, outside 10.3 °C2026-10-31: 31.2 kWh, outside 7.9 °C2026-11-01: 31.1 kWh, outside 7.5 °C2026-11-02: 32 kWh, outside 6.2 °C2026-11-03: 28.1 kWh, outside 8.6 °C2026-11-04: 29.1 kWh, outside 8.9 °C2026-11-05: 30.6 kWh, outside 9.9 °C2026-11-06: 29.9 kWh, outside 8.8 °C2026-11-07: 11 kWh, outside 7.8 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 4.222026-10-09: COP 4.542026-10-10: COP 4.182026-10-11: COP 4.12026-10-12: COP 4.792026-10-13: COP 4.642026-10-14: COP 4.222026-10-15: COP 4.732026-10-16: COP 4.042026-10-17: COP 3.712026-10-18: COP 3.952026-10-19: COP 4.392026-10-20: COP 4.422026-10-21: COP 3.952026-10-22: COP 3.82026-10-23: COP 3.872026-10-24: COP 3.882026-10-25: COP 3.962026-10-26: COP 4.22026-10-27: COP 4.272026-10-28: COP 4.252026-10-29: COP 4.182026-10-30: COP 4.092026-10-31: COP 3.822026-11-01: COP 3.922026-11-02: COP 3.782026-11-03: COP 4.022026-11-04: COP 42026-11-05: COP 3.992026-11-06: COP 4.012026-11-07: COP 3.7710-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050600246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.