Heatproof
Home / system #1248

Global Energy R290

Lancashire · Detached · 190 m² · Pre-1900 · 12 kW · radiators · installed by Adam Rowlandson

Last 7 days

169 hourly rows · MID-class heat meter present: yes
3.92efficiency (COP) over 169 hours, from the heat meter
better than 69% of the metered fleet in January 2026
Electricity used
213 kWh
Heat delivered
836 kWh (heat meter)
Estimate without heat meter
flow sensor 4.06 · temperature model 3.73
Mean outdoor temperature
8.3 °C · 140 space-heating hours
Flow temperature at 0 °C outside
40.9 °C (curve slope -0.48 per K)
Flow − return while heating
3.1 K
House needs at −3 °C
6.3 kW (unit rated 12 kW) · fit r² 0.25
Hot water
23% of electricity, COP 3.76
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day016322026-10-31: 21.4 kWh, outside 8.3 °C2026-11-01: 31.1 kWh, outside 7.5 °C2026-11-02: 32 kWh, outside 6.2 °C2026-11-03: 28.1 kWh, outside 8.6 °C2026-11-04: 29.1 kWh, outside 8.9 °C2026-11-05: 30.6 kWh, outside 9.9 °C2026-11-06: 29.9 kWh, outside 8.8 °C2026-11-07: 11 kWh, outside 7.8 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.762026-11-01: COP 3.922026-11-02: COP 3.782026-11-03: COP 4.022026-11-04: COP 42026-11-05: COP 3.992026-11-06: COP 4.012026-11-07: COP 3.7210-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506002468101214outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.