Heatproof
Home / system #1249

Viessmann Vitocal 150A

Bentlawnt, Shropshire · Detached · 140 m² · 2012 or newer · 10 kW · underfloor · installed by Josh Stead

Last 30 days

104 hourly rows · MID-class heat meter present: yes
5.32efficiency (COP) over 104 hours, from the heat meter
better than 99% of the metered fleet in January 2026
Electricity used
62 kWh
Heat delivered
327 kWh (heat meter)
Estimate without heat meter
flow sensor 5.38 · temperature model 4.66
Mean outdoor temperature
8.6 °C · 85 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
30.8 °C (curve slope -0.04 per K)
Flow − return while heating
3.8 K
House needs at −3 °C
3.5 kW (unit rated 10 kW) · fit r² 0.00
Hot water
11% of electricity, COP 4.38
infoUnit is rated 10 kW but the house needs about 3.5 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day08152026-10-18: 1.4 kWh, outside 12 °C2026-10-25: 10 kWh, outside 10 °C2026-10-26: 7.3 kWh, outside 9.7 °C2026-11-04: 8.2 kWh, outside 9.1 °C2026-11-05: 15.2 kWh, outside 7.9 °C2026-11-06: 13.9 kWh, outside 7.9 °C2026-11-07: 5.6 kWh, outside 6 °Cdaily COP (heat ÷ electricity)1352026-10-18: COP 5.582026-10-25: COP 5.422026-10-26: COP 5.422026-11-04: COP 5.492026-11-05: COP 5.072026-11-06: COP 5.242026-11-07: COP 5.4110-1810-2510-2611-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050604567891011121314outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.