Viessmann Vitocal 150A
Bentlawnt, Shropshire · Detached · 140 m² · 2012 or newer · 10 kW · underfloor · installed by Josh Stead
Last 30 days
105 hourly rows · MID-class heat meter present: yes
5.32efficiency (COP) over 105 hours, from the heat meter
better than 99% of the metered fleet in January 2026
better than 99% of the metered fleet in January 2026
- Electricity used
- 62 kWh
- Heat delivered
- 331 kWh (heat meter)
- Estimate without heat meter
- flow sensor 5.38 · temperature model 4.65
- Mean outdoor temperature
- 8.6 °C · 86 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 31.0 °C (curve slope -0.06 per K)
- Flow − return while heating
- 3.8 K
- House needs at −3 °C
- 3.5 kW (unit rated 10 kW) · fit r² 0.00
- Hot water
- 11% of electricity, COP 4.38
infoUnit is rated 10 kW but the house needs about 3.5 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.