Heatproof
Home / system #1412

Daikin Altherma 3

Erts, Andorra · Flat / appartment · 67 m² · 2012 or newer · 14 kW · underfloor

Last 30 days

721 hourly rows · MID-class heat meter present: no
2.92efficiency (COP) over 721 hours, from the heat meter
better than 7% of the metered fleet in January 2026
Electricity used
96 kWh
Heat delivered
281 kWh (heat meter)
Estimate without heat meter
flow sensor 3.10 · temperature model 5.08
Mean outdoor temperature
7.6 °C · 78 space-heating hours · cooling 3 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
27.1 °C (curve slope 0.02 per K)
Flow − return while heating
2.4 K
House needs at −3 °C
1.3 kW (unit rated 14 kW) · fit r² 0.17
Hot water
27% of electricity, COP 3.05
seriousWinter efficiency 2.92 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
warningOnly 2.4 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
infoUnit is rated 14 kW but the house needs about 1.3 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £5 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day0482026-10-08: 0.4 kWh, outside 8.5 °C2026-10-09: 1.1 kWh, outside 8.9 °C2026-10-10: 0.9 kWh, outside 11.1 °C2026-10-11: 2 kWh, outside 9.9 °C2026-10-12: 0.6 kWh, outside 13.5 °C2026-10-13: 1.9 kWh, outside 12 °C2026-10-14: 0.9 kWh, outside 11.7 °C2026-10-15: 0.5 kWh, outside 11.2 °C2026-10-16: 0.5 kWh, outside 12.5 °C2026-10-17: 1.1 kWh, outside 11.9 °C2026-10-18: 8.4 kWh, outside 9.1 °C2026-10-19: 3.2 kWh, outside 9.4 °C2026-10-20: 3.9 kWh, outside 8.9 °C2026-10-21: 2.8 kWh, outside 6.1 °C2026-10-22: 3.2 kWh, outside 5.9 °C2026-10-23: 6.2 kWh, outside 6.5 °C2026-10-24: 2.3 kWh, outside 5.4 °C2026-10-25: 5 kWh, outside 8.3 °C2026-10-26: 3.4 kWh, outside 8.8 °C2026-10-27: 2.3 kWh, outside 9.5 °C2026-10-28: 4.6 kWh, outside 8.5 °C2026-10-29: 2.4 kWh, outside 6.5 °C2026-10-30: 0.6 kWh, outside 5.2 °C2026-10-31: 1.5 kWh, outside 4.2 °C2026-11-01: 5.4 kWh, outside 5.8 °C2026-11-02: 6.7 kWh, outside 3.9 °C2026-11-03: 5.2 kWh, outside 2.5 °C2026-11-04: 3.6 kWh, outside 2.9 °C2026-11-05: 7 kWh, outside 2 °C2026-11-06: 7 kWh, outside 0.7 °C2026-11-07: 3.2 kWh, outside 0.4 °Cdaily COP (heat ÷ electricity)1352026-10-09: COP 02026-10-10: COP 0.052026-10-11: COP 2.682026-10-12: COP 02026-10-13: COP 0.62026-10-14: COP 0.022026-10-15: COP 0.042026-10-16: COP 0.042026-10-17: COP 0.012026-10-18: COP 3.942026-10-19: COP 1.262026-10-20: COP 1.82026-10-21: COP 2.22026-10-22: COP 2.462026-10-23: COP 3.432026-10-24: COP 2.12026-10-25: COP 3.462026-10-26: COP 4.342026-10-27: COP 2.782026-10-28: COP 4.062026-10-29: COP 1.712026-10-30: COP 02026-10-31: COP 02026-11-01: COP 4.182026-11-02: COP 3.42026-11-03: COP 2.842026-11-04: COP 3.792026-11-05: COP 3.372026-11-06: COP 2.472026-11-07: COP 3.5810-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-4-202468101214outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.