721 hourly rows · MID-class heat meter present: yes
4.25efficiency (COP) over 721 hours, from the heat meter better than 90% of the metered fleet in January 2026
Electricity used
166 kWh
Heat delivered
704 kWh (heat meter)
Estimate without heat meter
flow sensor 2.39 · temperature model 4.46
Mean outdoor temperature
7.4 °C · 268 space-heating hours
Flow temperature at 0 °C outside
23.6 °C (curve slope 0.90 per K)
Flow − return while heating
1.5 K
House needs at −3 °C
2.8 kW (unit rated 7 kW) · fit r² 0.15
Hot water
6% of electricity, COP 1.19
warningOnly 1.5 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
infoUnit is rated 7 kW but the house needs about 2.8 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “No heat on hot water due to split system”
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.