Heatproof
Home / system #169

Vaillant Arotherm Split

Swanage, Dorset · Mid-terrace · 70 m² · Pre-1900 · 7 kW · radiators · installed by Inafix

Last 7 days

169 hourly rows · MID-class heat meter present: yes
4.71efficiency (COP) over 169 hours, from the heat meter
better than 97% of the metered fleet in January 2026
Electricity used
19 kWh
Heat delivered
90 kWh (heat meter)
Estimate without heat meter
flow sensor 4.65 · temperature model 5.21
Mean outdoor temperature
10.0 °C · 14 space-heating hours
Flow temperature at 0 °C outside
34.5 °C (curve slope -0.47 per K)
Flow − return while heating
1.8 K
House needs at −3 °C
1.6 kW (unit rated 7 kW) · fit r² 0.00
Hot water
no hot-water flag in data
infoOnly 14 space-heating hours in this window
Space-heating findings need at least 60 hours with the compressor running below 15 °C outside. Choose a winter window or come back during the heating season.
noteOwner’s note on the source site: “No heat on hot water due to split system”

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day0242026-10-31: 0.8 kWh, outside 11.7 °C2026-11-01: 2.1 kWh, outside 8.6 °C2026-11-02: 2 kWh, outside 10.5 °C2026-11-03: 2.1 kWh, outside 9.8 °C2026-11-04: 2.5 kWh, outside 9.8 °C2026-11-05: 2.4 kWh, outside 9.6 °C2026-11-06: 4 kWh, outside 10.6 °C2026-11-07: 3.2 kWh, outside 9.1 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.312026-11-01: COP 4.462026-11-02: COP 4.652026-11-03: COP 4.622026-11-04: COP 4.82026-11-05: COP 4.92026-11-06: COP 4.792026-11-07: COP 4.6510-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.